Plan Review Notes
Plan Review Notes For Permit 20091217
Permit Number 20091217
Review Stop E
Sequence Number 1
Notes
Date Text
2020-10-26 20:17:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A 3-PHASE LOAD CALCULATION MUST BE DIVIDED BY 360
 NOT 208. DIVIDING SOLELY BY 208 IS FOR SINGLE-PHASE
 LOAD CALCULATION ONLY. THE SQUARE ROOT OF 3 WHICH IS
 1.732 MUST BE MULTIPLIED BY 208 GIVING YOU 360 THEN
 DIVIDE THE LOAD.
  
 2. PROVIDE ACCURATE LOAD CALCULATION TO INCLUDE ALL
 LOADS BOTH NEW AND EXISTING, NO AC/HEAT LOAD IS SHOWN
 NOR WATER HEATERS VAV'S ETC. NEC 215.2, 220, 408.30
  
 3. PROVIDE NOTE ON PLAN STATING LOW VOLTAGE SHOWN WILL
 REQUIRE SEPARATE PERMIT. FBC 107.2.1, 105.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  