| Plan Review Notes For Permit 20091217 |
| Permit Number |
20091217 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-23 13:27:00 | OFFICE RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE WINDOWS IN THE FIRE PARTITIONS TO | | | COMPLY WITH FBC TABLE 716.5 | | | 2) PLEASE REVISE THE DOOR SCHEDULE - THE DOOR "B" | | | SHOULD BE FIRE RATED AND SELF CLOSING FBC TABLE 716.5 | | | 3) SUITE "A" SHOWS A FIRE RATED PARTITION WITH A NON | | | FIRE RATED WALL DESIGNATION (A) - SHOULD BE (B). | | | |
|