| Date |
Text |
| 2020-10-05 13:47:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090781 |
| | 9/24/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GENERATOR SPECS SUBMITTED UNDER PERMIT- 20060140 |
| | SHOW A NATURAL GAS INPUT PRESSURE OF 3.5- 7 IN. W.C. |
| | FOR THE 22 KW GENERATOR, HOWEVER THE RISER DRAWING |
| | SHOWS A REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE. |
| | PLEASE CORRECT AND INDICATE THE MAKE AND MODEL OF THE |
| | SELECTED REGULATOR ON THE RISER. SUBMIT MARKED UP OR |
| | HIGHLIGHTED SPECS SHOWING THE MODEL, INLET AND OUTLET |
| | PRESSURES, SPRING SELECTION, AND ORIFICE SIZE- SECTION |
| | G2421.1 & G2421.2. SHOW THE REQUIRED PIPE UNIONS AT THE |
| | REGULATOR. |
| | |
| | 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT- |
| | 20060140) SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM |
| | COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF |
| | 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND |
| | DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |