Plan Review Notes
Plan Review Notes For Permit 20091183
Permit Number 20091183
Review Stop P
Sequence Number 2
Notes
Date Text
2020-10-08 10:48:572ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20091183
 10/8/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE COMMENTS LISTED BELOW FROM THE 1ST REVIEW STILL
 HAVE NOT BEEN ADDRESSED. NOTES IN CAP LETTERS HAVE BEEN
 ADDED TO EACH COMMENT- PLEASE COMPLY.
  
 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. PLEASE
 INCLUDE A SANITARY AND WATER RISER, AND PLUMBING
 FIXTURE AND DEVICE SCHEDULE. SHOW THE POINTS OF
 CONNECTIONS TO THE EXISTING WATER DISTRIBUTION AND
 SANITARY DRAINAGE SYSTEMS- SECTION 107.3.5.1.3 WPB
 AMENDMENTS. THIS IS A SEPARATE PERMIT AND NOT A
 REVISION TO THE PREVIOUSLY ISSUED PLANS UNDER PERMITS
 16090622 & 19061299. COMPLETE PLUMBING PLANS AND
 SPECIFICATIONS ARE REQUIRED INCLUDING THE REQUESTED
 RISER DRAWINGS; FIXTURE CALCULATIONS; FIXTURE,
 EQUIPMENT, AND DEVICE SCHEDULES; PIPING AND INSULATION
 SPECIFCATIONS ETC. THE RECORDED PLANS ON FILE FOR
 PERMIT- 16090622 SHOWS ONLY SANITARY DRAINAGE CLEANOUT
 STUB-UPS, AND A WATER SUPPLY SHUT OFF VALVE AT EACH
 RESTROOM LOCATION. RECORDED PLANS FOR PERMIT 19061299
 DO NOT SHOW ANY PLUMBING WORK IN THE C BUILDING.
 PLEASE NOTE THE PLUMBING PLANS FOR PERMIT 16090622 SHOW
 PLUMBING STUBS FOR THE RESTROOMS IN STUDIO'S C6 AND C9
 WHICH APPEAR TO HAVE BEEN ELIMINATED, AND A NEW
 ACCESSIBLE COUNTER AND SINK TO BE INSTALLED. PLEASE
 PROVIDE ARCHITECTUAL DETAILS FOR INSTALLATION OF THE
 COUNTER AND SINK TO MEET COMPLIANCE WITH SECTIONS
 606.2, 305, 306, 308, & 309 FBC ACC. PLEASE PROVIDE
 RISER DRAWINGS AND ADD THE SINK TO THE FIXTURE
 SCHEDULE.
  
 2) INDICATE HOW THE REQUIRED TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES PER SECTION 416.5 FBC P, AND
 SHOW THE SOURCE OF REQUIRED HOT WATER- SECTION 607.1.
 PLEASE SEE NOTES ADDED TO COMMENT #1 ABOVE. THE
 SELECTED WATER HEATER SHALL BE EQUIPPED WITH AN ASSE
 1070 WATER TEMPERATURE LIMITING DEVICE THAT LIMITS THE
 WATER TEMPERATURE TO 110 DEGREES F, OR APPROVED MIXING
 VALVES SHALL BE INSTALLED- SECTION 607.1.2 FBC P.
  
 3) A2.1: ACCESSIBILITY CORRECTIONS NEEDED PER THE FBC
 ACC:
 D) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 306 AND 606.2. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  