2020-09-30 10:09:561ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20091183
 9/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. PLEASE
 INCLUDE A SANITARY AND WATER RISER, AND PLUMBING
 FIXTURE AND DEVICE SCHEDULE. SHOW THE POINTS OF
 CONNECTIONS TO THE EXISTING WATER DISTRIBUTION AND
 SANITARY DRAINAGE SYSTEMS- SECTION 107.3.5.1.3 WPB
 AMENDMENTS.
  
 2) INDICATE HOW THE REQUIRED TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES PER SECTION 416.5 FBC P, AND
 SHOW THE SOURCE OF REQUIRED HOT WATER- SECTION 607.1.
  
 3) A2.1: ACCESSIBILITY CORRECTIONS NEEDED PER THE FBC
 ACC:
  
 A) THE MOUNTING HEIGHTS OF THE GRAB BARS IS NOT SHOWN.
 THE HEIGHTS SHALL BE IN COMPLIANCE WITH- SECTION 609.4.
 PLEASE SEE FIGURE 604.5.2 FOR LOCATION OF REAR GRAB BAR
 BEHIND THE WATER CLOSET.
  
 B) LOCATION OF THE WATER CLOSET FLUSH CONTROL NOT
 SHOWN- SECTION 604.6.
  
 C) THE 40" HEIGHT OF THE MIRROR SHALL BE MEASURED FROM
 THE FINISHED FLOOR TO THE REFLECTIVE SURFACE- SECTION
 603.3.
  
 D) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN-
 SECTIONS 306 AND 606.2.
  
 4) A2.1: PLEASE REFER TO SECTION 310.3 FBC P: THE
 INTERIOR WALL FINISH IN THE RESTROOM SHALL BE IN
 ACCORDANCE WITH SECTION 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 EXCEPTION: THIS SECTION DOES NOT APPLY TO THE FOLLOWING
 BUILDINGS AND SPACES:
 1. DWELLING UNITS AND SLEEPING UNITS.
 2. TOILET ROOMS THAT ARE NOT ACCESSIBLE TO THE PUBLIC
 AND THAT HAVE NOT MORE THAN ONE WATER CLOSET.
  
 THE PLAN IS INDICATING EPOXY- PAINTED DRYWALL, HOWEVER
 IF THE RESTROOM IS OPEN TO THE PUBLIC THEN
 EPOXY-PAINTED DRYWALL DOES NOT MEET COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  