| Date |
Text |
| 2020-09-30 10:09:56 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20091183 |
| | 9/30/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE PLUMBING PLANS AND SPECIFICATIONS. PLEASE |
| | INCLUDE A SANITARY AND WATER RISER, AND PLUMBING |
| | FIXTURE AND DEVICE SCHEDULE. SHOW THE POINTS OF |
| | CONNECTIONS TO THE EXISTING WATER DISTRIBUTION AND |
| | SANITARY DRAINAGE SYSTEMS- SECTION 107.3.5.1.3 WPB |
| | AMENDMENTS. |
| | |
| | 2) INDICATE HOW THE REQUIRED TEMPERED WATER WILL BE |
| | PROVIDED TO THE LAVATORIES PER SECTION 416.5 FBC P, AND |
| | SHOW THE SOURCE OF REQUIRED HOT WATER- SECTION 607.1. |
| | |
| | 3) A2.1: ACCESSIBILITY CORRECTIONS NEEDED PER THE FBC |
| | ACC: |
| | |
| | A) THE MOUNTING HEIGHTS OF THE GRAB BARS IS NOT SHOWN. |
| | THE HEIGHTS SHALL BE IN COMPLIANCE WITH- SECTION 609.4. |
| | PLEASE SEE FIGURE 604.5.2 FOR LOCATION OF REAR GRAB BAR |
| | BEHIND THE WATER CLOSET. |
| | |
| | B) LOCATION OF THE WATER CLOSET FLUSH CONTROL NOT |
| | SHOWN- SECTION 604.6. |
| | |
| | C) THE 40" HEIGHT OF THE MIRROR SHALL BE MEASURED FROM |
| | THE FINISHED FLOOR TO THE REFLECTIVE SURFACE- SECTION |
| | 603.3. |
| | |
| | D) KNEE AND TOE CLEARANCES FOR THE LAVATORY NOT SHOWN- |
| | SECTIONS 306 AND 606.2. |
| | |
| | 4) A2.1: PLEASE REFER TO SECTION 310.3 FBC P: THE |
| | INTERIOR WALL FINISH IN THE RESTROOM SHALL BE IN |
| | ACCORDANCE WITH SECTION 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | EXCEPTION: THIS SECTION DOES NOT APPLY TO THE FOLLOWING |
| | BUILDINGS AND SPACES: |
| | 1. DWELLING UNITS AND SLEEPING UNITS. |
| | 2. TOILET ROOMS THAT ARE NOT ACCESSIBLE TO THE PUBLIC |
| | AND THAT HAVE NOT MORE THAN ONE WATER CLOSET. |
| | |
| | THE PLAN IS INDICATING EPOXY- PAINTED DRYWALL, HOWEVER |
| | IF THE RESTROOM IS OPEN TO THE PUBLIC THEN |
| | EPOXY-PAINTED DRYWALL DOES NOT MEET COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |