| Plan Review Notes For Permit 20091176 |
| Permit Number |
20091176 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-14 14:27:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PANEL SCHEDULE REQUIRED | | | | | | PROVIDE PANEL SCHEDULE INDICATING ANY NEW CIRCUITS, THE | | | WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR | | | GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. | | | NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, RE3902 | | | | | | 2) PROVIDE A LOAD CALCULATION PER 215.5 | | | | | | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. | | | NEC 220; FBC RE3602.3 | | | | | | 3) FEEDER TO PANEL WILL HAVE TO BE ROUTED UNDERGROUND | | | FROM METER TO PANEL OR A MAIN WILL BE REQUIRED OUTSIDE | | | AT METER. | | | | | | |
|