Plan Review Notes
Plan Review Notes For Permit 20091176
Permit Number 20091176
Review Stop E
Sequence Number 1
Notes
Date Text
2020-10-14 14:27:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PANEL SCHEDULE REQUIRED
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW CIRCUITS, THE
 WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR
 GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE.
 NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, RE3902
  
 2) PROVIDE A LOAD CALCULATION PER 215.5
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE3602.3
  
 3) FEEDER TO PANEL WILL HAVE TO BE ROUTED UNDERGROUND
 FROM METER TO PANEL OR A MAIN WILL BE REQUIRED OUTSIDE
 AT METER.
  
  