2021-02-05 14:46:30CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET A.1 (PROPOSED PLAN VIEW) AND E.1 -- A.1 SHOWS
 THREE METERS WHILE RISER DIAGRAM AND POWER LAYOUT ON
 E.1 SHOWS ONLY TWO. PLEASE EXPLAIN AND CORRECT
 DISCREPANCIES. FBC 107
 2) ELECTRICAL DRAWINGS FOR OTHER UNIT (PERMIT 20121069)
 SHOWS THREE PANELS ON RISER DIAGRAM WHILE THIS PERMIT
 ONLY SHOWS TWO PANELS. PLEASE EXPLAIN AND CORRECT
 DISCREPANCIES.IF ONLY TWO PANELS AND TWO METERS, PERMIT
 20121069 WILL NEED TO BE REVISED AS WELL.
 3) SHEET E.1: LOAD CALCULATIONS ARE FOR THREE PANELS
 (A, B, AND C) WHILE RISER DIAGRAM ONLY SHOWS TWO
 PANELS. PLEASE UPDATE LOAD CALCULATIONS FOR ENTIRE
 SERVICE AS WELL AS SEPARATE PANELS (A AND B IF ONLY TWO
 PANELS WILL BE USED). FBC 107
 4) PLEASE SPECIFY AIC RATINGS FOR SERVICE DISCONNECTS
 AND PANELS A AND B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved