| 2021-02-05 14:46:30 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) SHEET A.1 (PROPOSED PLAN VIEW) AND E.1 -- A.1 SHOWS |
| | THREE METERS WHILE RISER DIAGRAM AND POWER LAYOUT ON |
| | E.1 SHOWS ONLY TWO. PLEASE EXPLAIN AND CORRECT |
| | DISCREPANCIES. FBC 107 |
| | 2) ELECTRICAL DRAWINGS FOR OTHER UNIT (PERMIT 20121069) |
| | SHOWS THREE PANELS ON RISER DIAGRAM WHILE THIS PERMIT |
| | ONLY SHOWS TWO PANELS. PLEASE EXPLAIN AND CORRECT |
| | DISCREPANCIES.IF ONLY TWO PANELS AND TWO METERS, PERMIT |
| | 20121069 WILL NEED TO BE REVISED AS WELL. |
| | 3) SHEET E.1: LOAD CALCULATIONS ARE FOR THREE PANELS |
| | (A, B, AND C) WHILE RISER DIAGRAM ONLY SHOWS TWO |
| | PANELS. PLEASE UPDATE LOAD CALCULATIONS FOR ENTIRE |
| | SERVICE AS WELL AS SEPARATE PANELS (A AND B IF ONLY TWO |
| | PANELS WILL BE USED). FBC 107 |
| | 4) PLEASE SPECIFY AIC RATINGS FOR SERVICE DISCONNECTS |
| | AND PANELS A AND B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |