Plan Review Notes For Permit 20091175
Permit Number 20091175
Review Stop R
Sequence Number 2
Notes
Date Text
2020-11-23 09:44:00PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND ROOFING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVEDE THE PRODUCT APPROVAL FOR THE
 ROOFING MATERIALS TO BE USED. AS PER PLAN SHEET S.2, IT
 APPEARS THAT THE INTENDED PRODUCT APPROVAL IS NOA #
 16?0413.06. THIS NOA NEEDS TO BE SUBMITTED WITH THE
 SELECTED OPTION IDENTIFIED
 (MARKED/CIRCLED/HIGHLIGHTED). THE OPTION SELECTED MUST
 MEET THE WINDLOAD PRESSURES REQUIRED.