| 2020-11-19 16:10:28 | 1ST REVIEW FBC-2017 RES. | | | PERMIT- 20091175 | | | 11/19/20 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1/M1: THE RISER DRAWING AND THE PLUMBING PLAN | | | DO NOT MATCH. THE RISER SHOWS A DOUBLE LAV SINK, THE | | | PLAN SHOWS A SINGLE. THE RISER SHOWS A WASHING MACHINE, | | | THE PLAN DOES NOT SHOW A WASHING MACHINE. | | | | | | 2) P1/M1: PROVIDE THE EFFICIENCY RATINGS OF THE NEW | | | TANKLESS WATER HEATERS, AND ENTER THE DATA IN THE | | | ENERGY COMPLIANCE FORM R405-2017. | | | | | | 3) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION | | | 105.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|