2020-11-19 16:10:281ST REVIEW FBC-2017 RES.
 PERMIT- 20091175
 11/19/20
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1/M1: THE RISER DRAWING AND THE PLUMBING PLAN
 DO NOT MATCH. THE RISER SHOWS A DOUBLE LAV SINK, THE
 PLAN SHOWS A SINGLE. THE RISER SHOWS A WASHING MACHINE,
 THE PLAN DOES NOT SHOW A WASHING MACHINE.
  
 2) P1/M1: PROVIDE THE EFFICIENCY RATINGS OF THE NEW
 TANKLESS WATER HEATERS, AND ENTER THE DATA IN THE
 ENERGY COMPLIANCE FORM R405-2017.
  
 3) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  