| Plan Review Notes For Permit 20091175 |
| Permit Number |
20091175 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-11-23 09:34:19 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW FAILED: | | | | | | FBC B 107.2.1, PLEASE PROVIDE A RESPONSE LETTER WITH | | | THE CHANGES MADE FOR THE INSULATION TO BE USED AS THIS | | | IS STILL NOT CLEAR AS TO WHAT IS INTENDED FOR USE. SEE | | | THE NOTES BELOW: | | | | | | 1) ON PLAN SHEET A.2 (SHOWS R?19 WITH 1" SPACE FOR | | | CROSS VENTILLATION). | | | 2) FBC ENERGY CONSERVATION PAGE R?56 PRESCRIPTIVE | | | REQUIREMENTS (SHOWS CLIMATE ZONE 1, R?30). | | | 3) FBC ENERGY CONSERVATION PAGE R?56 INSTALLED VALUES | | | (SHOWS R?20 SPRAY FOAM). | | | 4) FBC ENERGY EFFICIENCY RESIDENTIAL PERFORMANCE | | | METHOD, PAGE 3, CEILING INSULATION TYPE (SHOWS BLOWN). |
|