2020-09-30 10:16:18PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW DENIED:
  
 FBC RM TABLE M1506.2, THE BATHROOM EXHAUST DUCT NEEDS
 TO BE CHANGED FROM 3" TO 4" DIAMETER AND THE BATHROOM
 EXHAUST FANS NEED TO MOVE A HIGHER CFM THAN 50 CFM. 70
 CFM FANS WITH 4" DUCTS SHOULD MEET THE REQUIREMENTS FOR
 A 50 CFM SYSTEM PER FBC RM TABLE M1506.2.