2020-10-07 16:01:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS 2/0S IN MAST PLEASE SUBMIT A LOAD
 CALCULATION FOR THESE 2/0S.
  
 PLAN SHOWS PANEL IN THIS BUILDING, IS IT REMOTE FROM
 SERVICE IF SO PLEASE ESTABLISH GROUNDING ELECTRODE
 SYSTEM AT THIS BUILDING 250.32(A)