Plan Review Notes
Plan Review Notes For Permit 20091170
Permit Number 20091170
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-07 11:01:03REPAIRS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE AN EVALUATION REPORT FROM A LICENSED
 ARCHITECT OR ENGINEER FBC EXISTING BUILDING 606.2.2.1
 EVALUATION.
 THE BUILDING SHALL BE EVALUATED BY A REGISTERED DESIGN
 PROFESSIONAL, AND THE EVALUATION FINDINGS SHALL BE
 SUBMITTED TO THE CODE OFFICIAL. THE EVALUATION SHALL
 ESTABLISH WHETHER THE DAMAGED BUILDING, IF REPAIRED TO
 ITS PREDAMAGE STATE, WOULD COMPLY WITH THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING FOR LOAD
 COMBINATIONS THAT INCLUDE WIND OR EARTHQUAKE EFFECTS,
 EXCEPT THAT THE SEISMIC FORCES SHALL BE THE REDUCED
 FLORIDA BUILDING CODE, BUILDING-LEVEL SEISMIC FORCES.
 2) PLEASE PROVIDE CONSTRUCTION DRAWINGS FOR ANY
 STRUCTURAL REPAIRS REQUIRED BY THE EVALUATION REPORT.
 3) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATIONS OF
 THE REPAIRS AND WRITE THE SCOPE OF WORK ON THE PLAN.