Plan Review Notes
Plan Review Notes For Permit 20091144
Permit Number 20091144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-09-29 11:26:21 
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN
 THE
 MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH
 ELECTRICAL
 LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL
 OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS
 UPON LOSS OF POWER TO THE SENSOR OR TO THE PART OF THE
 ACCESS
 CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF
 THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS
 SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) VERTICALLY
 ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE
 SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN
 DIRECT INTERRUPTION OF POWER TO THE LOCK ? INDEPENDENT
 OF THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL
 REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN
 THE
 DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN
 MANUALLY RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE
 BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR
 LEAVES.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE
 DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES
 SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN
 EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.