| 2021-03-16 12:19:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS & MECHANICAL - THEE ARE NO INDICATIONS OF A |
| | HOOD NOR A FIRE SUPPRESSION SYSTEM OVER THE COOKING |
| | EQUIPMENT. |
| | |
| | PER NFPA 1 |
| | |
| | 50.2 GENERAL REQUIREMENTS. |
| | 50.2.1 GENERAL. |
| | 50.2.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
| | SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN |
| | EXHAUST |
| | SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND |
| | PERFORMANCE |
| | REQUIREMENTS OF THIS CHAPTER. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC CODE |
| | REFRERNCES AND NARRATIVE STATING WHY IT IS NOT |
| | REQUIRED. |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF FIRE LINE UNDERGROUND DEMO |
| | AND NEW LINE. |
| | |
| | ALL FIRE LINE WORK SHALL COMPLY WITH NFPA 24, BE |
| | INSTALLED BY A CERTIFIED UNDERGROUND CONTRACTOR AND BE |
| | SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 3) SHEET LS & A1 - THERE IS AN INDICATION OF A THE |
| | FRONT BATHROOM, WOMAN 111, DOOR THAT OPENS OUT INTO THE |
| | EXIT CORRIDOR AND ENCROACHES ON THE REQUIRED EGRESS |
| | PATH WIDTH. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL |
| | LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| | AN AISLE, A CORRIDOR, |
| | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF |
| | THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL |
| | NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR |
| | LEAF IS EQUIPPED |
| | WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT |
| | REQUIRED BY THE PROVISIONS |
| | OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL. |
| | |
| | PLEASE REVIEW AND CORRECT, SWING THE DOOR IN OR PROVIDE |
| | SPECIFIC DIMENSIONS MEETING THE REQUIREMENTS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |