| 2021-01-07 13:07:59 | 01/07/20 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | THIS IS THE THIRD PLAN REVIEW THAT HAS NOT PASSED. |
| | PLEASE GET WITH THE PLAN REVIEWER AND MAKE AN |
| | APPOINTMENT TO COME INTO THE BUILDING DEPARTMENT TO |
| | EXPLAIN WHAT IS NEEDED. |
| | |
| | 1. PLEASE PROVIDE ANCHORING DETAIL THAT IS NOT A COPY |
| | OF THE SIGNATURE OR SEAL, WHICH IS NOT IN ACCORDANCE |
| | WITH FLORIDA ADMINISTRATIVE CODE PER 61G15-23.001, |
| | FLORIDA STATUTE 471, OR PROVIDE THE DOCUMENT FOR YOUR |
| | TIE-DOWN WITHOUT A SEAL AND SIGNATURE, NO COPIES. |
| | |
| | 2. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS |
| | SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL ON THE |
| | DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE |
| | CODE SEC. 61G15-23.005. |
| | |
| | 3. THE ANCHORING INSTALLATION SEEMS TO BE ABOVE GROUND, |
| | AND THIS IS AN UNDERGROUND TANK; PLEASE CLARIFY. PLEASE |
| | SHOW THE LP GAS CONTAINER'S DEPTH BELOW GRADE TO COMPLY |
| | WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 4. THE DETAILS SUBMITTED FOR THE TYPE OF CATHODIC |
| | PROTECTION DO NOT HAVE THE SIZE (LBS.) & THE NUMBER OF |
| | MAGNESIUM BAG(S), SIZE & TYPE, OR HOW MUCH WATER TO |
| | ACTIVATE IT. |
| | |
| | 5. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE |
| | GENERATOR UNIT AT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |