Plan Review Notes
Plan Review Notes For Permit 20091096
Permit Number 20091096
Review Stop G
Sequence Number 1
Notes
Date Text
2021-01-07 13:07:5901/07/20 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THIS IS THE THIRD PLAN REVIEW THAT HAS NOT PASSED.
 PLEASE GET WITH THE PLAN REVIEWER AND MAKE AN
 APPOINTMENT TO COME INTO THE BUILDING DEPARTMENT TO
 EXPLAIN WHAT IS NEEDED.
  
 1. PLEASE PROVIDE ANCHORING DETAIL THAT IS NOT A COPY
 OF THE SIGNATURE OR SEAL, WHICH IS NOT IN ACCORDANCE
 WITH FLORIDA ADMINISTRATIVE CODE PER 61G15-23.001,
 FLORIDA STATUTE 471, OR PROVIDE THE DOCUMENT FOR YOUR
 TIE-DOWN WITHOUT A SEAL AND SIGNATURE, NO COPIES.
  
 2. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL ON THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005.
  
 3. THE ANCHORING INSTALLATION SEEMS TO BE ABOVE GROUND,
 AND THIS IS AN UNDERGROUND TANK; PLEASE CLARIFY. PLEASE
 SHOW THE LP GAS CONTAINER'S DEPTH BELOW GRADE TO COMPLY
 WITH NFPA 58 SEC. 6.6.6.1.
  
 4. THE DETAILS SUBMITTED FOR THE TYPE OF CATHODIC
 PROTECTION DO NOT HAVE THE SIZE (LBS.) & THE NUMBER OF
 MAGNESIUM BAG(S), SIZE & TYPE, OR HOW MUCH WATER TO
 ACTIVATE IT.
  
 5. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE
 GENERATOR UNIT AT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  