2020-09-29 09:50:23JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL16717-R6 HAS BEEN
 REVISED TO FL16717-R9. PLEASE PROVIDE A COMPLETE SET
 INCLUDING MISSING EVALUATION REPORT WITH LIMITATIONS
 PAGE. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 AS PER RULE 61G20-3.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16717-R6 ROOF SYSTEM #W-68, DOES NOT MEET
 THE MINIMUM DESIGN PRESSURES FOR ZONE 3 AND WOULD
 REQUIRE SIGNED AND SEALED ENHANCE NAILING CALCULATIONS.
 PLEASE PROVIDE OR CHOOSE ANOTHER SYSTEM THAT MEET THE
 MINIMUM DESIGN PRESSURES FOR ALL THREE ZONES.
  