2020-09-28 12:57:3309/28/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT THE POOL PUMP CURVE FROM THE
 MANUFACTURE SPECIFICATION ALONG WITH THE PUMP MODEL.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 2. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES, HEATER
 (MISSING), FILTER, ETC. BUT THERE IS NO FRICTION LOSS
 ASSOCIATED WITH THESE ITEMS. PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. THE CARTRIDGE FILTER SPECIFICATION DOES NOT MATCH
 THE ONES IN CALCULATION, THE ONE IN TDH IS A CL1200
 PLEASE PROVIDE CORRECT ONES PER THE WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 4. PLEASE PROVIDE THE HEAT PUMP POOL HEATERS
 SPECIFICATION TO VERIFY COMPLIANCE AS IT SHALL HAVE A
 MINIMUM COP OF 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI
 1160, TABLE 2, STANDARD RATING CONDITIONS ? LOW AIR
 TEMPERATURE. A TEST REPORT FROM AN INDEPENDENT
 LABORATORY IS REQUIRED TO VERIFY PROCEDURE COMPLIANCE
 PER THE 2017 FBC-ENERGY ? SEC. R 403.10.5.
  
 5. PLEASE SHOW THE POOL HEATER IN THE PIPING SCHEMATIC
 SUBMITTED PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  