| 2020-09-28 12:57:33 | 09/28/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT THE POOL PUMP CURVE FROM THE |
| | MANUFACTURE SPECIFICATION ALONG WITH THE PUMP MODEL. |
| | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC |
| | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS |
| | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| | CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1. |
| | |
| | 2. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW |
| | THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS. |
| | THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES, HEATER |
| | (MISSING), FILTER, ETC. BUT THERE IS NO FRICTION LOSS |
| | ASSOCIATED WITH THESE ITEMS. PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THE CARTRIDGE FILTER SPECIFICATION DOES NOT MATCH |
| | THE ONES IN CALCULATION, THE ONE IN TDH IS A CL1200 |
| | PLEASE PROVIDE CORRECT ONES PER THE WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | |
| | 4. PLEASE PROVIDE THE HEAT PUMP POOL HEATERS |
| | SPECIFICATION TO VERIFY COMPLIANCE AS IT SHALL HAVE A |
| | MINIMUM COP OF 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI |
| | 1160, TABLE 2, STANDARD RATING CONDITIONS ? LOW AIR |
| | TEMPERATURE. A TEST REPORT FROM AN INDEPENDENT |
| | LABORATORY IS REQUIRED TO VERIFY PROCEDURE COMPLIANCE |
| | PER THE 2017 FBC-ENERGY ? SEC. R 403.10.5. |
| | |
| | 5. PLEASE SHOW THE POOL HEATER IN THE PIPING SCHEMATIC |
| | SUBMITTED PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |