| 2020-09-29 14:48:01 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20091056 |
| | 9/29/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P101: REMOVE OR CORRECT THE ELECTRIC WATER |
| | HEATER LABELS ON THE PLAN UNDER THE PHOTO AND DETAIL. |
| | THE WH IS A GAS-FIRED TANKLESS WATER HEATER THAT WAS |
| | INSTALLED UNDER PERMIT- 20080653. |
| | |
| | 2) P101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER |
| | HEATER INDICATING MAKE, MODEL NUMBER, AND EFFICIENCY |
| | RATING- SECTION 107.2.1 WPB & TABLE C404.2 FBC EC. |
| | PLEASE NOTE THE RHEEM MODEL SHOWN IN THE PHOTO DOES NOT |
| | MATCH THE NAVIEN MODEL NUMBER SHOWN ON THE GAS DRAWINGS |
| | UNDER PERMIT- 20080653- NAVIEN NPE-240 A. SUBMIT A |
| | MANUFACTURER?S PRODUCT SPEC SHEET AND INSTALLATION |
| | GUIDELINES FOR THE WATER HEATER SHOWING RECOMMENDED |
| | CLEARANCES FOR SERVICE ACCESS AND VENTING- SECTION |
| | 624.1 FBC FG. PLEASE DO NOT SUBMIT THE ENTIRE INSTALL |
| | MANUAL JUST THE RELEVANT SHEETS. THE ENTIRE MANUAL |
| | SHALL BE ONSITE FOR INSPECTION. |
| | |
| | 3) P101: REVISE THE WATER RISER TO MATCH WITH THE WATER |
| | PLAN- SECTION 107.2.1 WPB. |
| | |
| | 4) P101: INDICATE HOW CONDENSATE FROM THE WATER HEATER |
| | WILL DISCHARGE TO AN APPROVED PLACE OF DISPOSAL- |
| | SECTION 307.2 FBC FG. |
| | |
| | 5) P101: THE SANITARY RISER SHOWS TWO UNIDENTIFIED |
| | TRAPPED FIXTURES SHARING A COMMON VENT THAT ARE NOT |
| | SHOWN ON THE PLANS OR WATER RISER. PLEASE IDENTIFY AND |
| | SHOW THE LOCATIONS OF THE FIXTURES ON THE FLOOR PLAN OR |
| | CORRECT THE RISER- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |