| 2020-09-29 12:07:43 | 2ND REVIEW FBC-2017 RES. PLUMBING. |
| | PERMIT-20091013 |
| | 9/29/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-2 & P-3: THE SELECTED RHEEM RETEX-18 IS |
| | UNDERSIZED FOR REQUIRED HOT WATER GPM FLOW TO THE |
| | FIXTURES. THE MANUFACTURER'S TEMPERATURE RISE CHART FOR |
| | THE SELECTED RHEEM RETEX-18 SHOWS A MAX 4.0 GPM FLOW AT |
| | A 31-DEGREE F TEMPERATURE RISE. PLEASE NOTE HOT WATER |
| | AT A TEMPERATURE OF 110 DEGREES F SHALL BE PROVIDED TO |
| | THE FIXTURES WHERE REQUIRED- SECTION P2801.1 FBC RES. |
| | REFER TO TABLE P2903.1 FBC P AND SELECT A WATER HEATER |
| | WITH THE CAPACITY TO PROVIDE THE REQUIRED GPM HOT WATER |
| | FLOW TO ALL FIXTURES AND APPLIANCES. INDICATE THE MAKE |
| | AND MODEL ON THE CORRECTED PLANS AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS THAT INCLUDE THE |
| | TEMPERATURE RISE CHART. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |