| Date |
Text |
| 2020-10-09 09:50:22 | 1) SHT. A.1 - H.C.T.R. DETAIL PLAN - NOTES #1 & #3 - |
| | THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER FBC-ACCESS. SEC. 609.4. REVISE THE |
| | NOTES. |
| | 2) THE TOILET PAPER DISPENSERS SHALL BE LOCATED 7-9 |
| | INCHES IN FRONT OF THE WATER CLESET MEASURED TO THE |
| | CENTERLINE OF THE DISPENSER PER FBC-ACCESS. SEC. 604.7. |
| | 3) SHT. A.1 - H.C.T.R. DETAIL - THE DOORS SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED |
| | FOR ANY FIXTURE PER FBC-ACCESS. SEC.603.2.3. (SEE |
| | EXCEPTION #2). |
| | 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE STAFF |
| | AND EXAM SINK PER FBC-ACCESS.SEC.606.2. A MINIMUM 30 |
| | INCH WIDE CLEAR FLOOR SPACE COMPLYING WITH |
| | FBC-ACCESS.SEC. 305 POSITIONED FOR A FORWARD APPROACH, |
| | SHALL BE PROVIDED FOR THE EXAM ROOM SINK. A PARALLEL |
| | APPROACH COMPLYNG WITH SEC. 305 SHALL BE PERMITTED TO |
| | THE STAFF ROOM SINK. |
| | 5) EPOXY PAINT ON THE TOILET ROOM WALLS DOES NOT COMPLY |
| | WITH FBC-BUILDING SEC.12110.2.2. WALLS AND PARTITIONS |
| | WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM) |
| | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. THE WALLS |
| | AROUND THE JANITOR SINK SHALL ALSO COMPLY. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE |
| | TOILET ROOMS PER FBC-PLUMBING SEC.416.5.TEMPERED WATER |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | 8) SIZE THE DRAINS FOR THE STAFF AND EXAM SINKS ON THE |
| | SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) ONLY THE PLUMBING FIXTURES WITHIN THE BATHROOM GROUP |
| | ARE PERMITTED TO BE VENTED BY A HORIZONTAL WET VENT PER |
| | FBC-PLUMBING SEC.912.1. AS DRAWN, THE SANITARY RISER |
| | DIAGRAM DOES NOT COMPLY. |
| | 10) THE RISER DIAGRAM REFERS TO THE USE OF OFFSET |
| | FLANGES.THESE FLANGES CANNOT BE USED PER FBC-PLUMBING |
| | SEC.706.2. |
| | 11) SHOW THE SIZE OF THE EXISTING SANITARY DRAIN |
| | PIPING. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |