| 2020-11-06 13:44:28 | THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ******COMMENTS WERE NOT ADDRESSED AT ALL. |
| | NO RESPONSE ON THE RESUBMITTAL. |
| | |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED REVISED |
| | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE |
| | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES |
| | APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS |
| | PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- STOREFRONT IS NOT PART OF THIS PERMIT. |
| | |
| | 2- OK |
| | |
| | 3- SHEET A4.2: |
| | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW |
| | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 |
| | FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| | |
| | RESPONSE: |
| | DETAIL #16 WAS REVISED BUT STILL SHOWS NO HANDRAILS ON |
| | BOTH SIDES OF THE RAMP. IT SHOWS ONLY ONE SIDE WITH |
| | HANDRAIL. REVISE AS REQUIRED. |
| | |
| | B) OK. |
| | |
| | C)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE |
| | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. |
| | SEC. 505.10.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | D) DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT |
| | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT |
| | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. REVISE |
| | AS REQUIRED. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | 4- SHEET A4.3: |
| | A) OK |
| | |
| | B) OK |
| | |
| | C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE |
| | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES |
| | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. |
| | SEC. 1603.1 FBC-BUILDING. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. THERE ARE NOT DETAILS/SPECS FOR FOOTINGS |
| | SIZES, REINFORCEMENT FOR SIGNAGE WALL. |
| | |
| | D) OK |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |