| Date |
Text |
| 2021-01-07 16:57:25 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 505, |
| | SEC. 506 FBC-EXISTING BUILDING AND SEC. R101.5 |
| | FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | 1(A)OWNER OR OWNER'S ARCHITECT OR OTHER OWNER LEGALLY |
| | AUTHORIZED AGENT NEEDS TO SIGN AND DATE THE BOTTOM OF |
| | FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S OR |
| | AUTHORIZED AGENT CERTIFICATION. |
| | |
| | |
| | 1(B)BUILDER NAME DOESN'T MATCH BUILDER APPLYING FOR THE |
| | WORK. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 2- OK |
| | 3- OK |
| | |
| | ORIGINAL COMMENT: |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | THERE IS NO WAY OF KNOWING WHICH PRODUCT APPROVALS THE |
| | ARCHITECT REVIEWED/APPROVED. PRODUCT APPROVALS |
| | SUBMITTED DON'T SHOW ANY INDICATION THAT THEY WERE |
| | REVIEWED AND APPROVED BY THE ARCHITECT OF RECORD. THE |
| | ONLY RESPONSE FROM ARCHITECT WAS "SEE APPROVED PRODUCT |
| | APPROVALS FOR INSTALLATION". THERE IS NO REVIEW STAMP |
| | ON THE PRODUCT APPROVAL OR ANY LIST OF SPECIFIC PRODUCT |
| | APPROVAL NUMBERS AND MODELS THAT WERE REVIEWED/APPROVED |
| | BY THE ARCHITECT. |
| | ARCHITECT TO PROVIDE REVIEW STAMP ON EACH PRODUCT |
| | APPROVAL OR PROVIDE LETTER CLEARLY LISTING EACH PRODUCT |
| | APPROVAL SPECIFIC NUMBER AND MODEL. |
| | |
| | 5- OK |
| | 6- OK |
| | 7- OK |
| | 8- OK |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |