| Plan Review Notes For Permit 20090918 |
| Permit Number |
20090918 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-09 08:09:16 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC B 107.2.1, PLEASE CONFIRM THAT THE WIDTH OF THE | | | GENERATOR SLAB IS ACCEPTABLE TO MEET THE REQUIREMENTS | | | OF THE MANUFACTURER'S SPECIFICATIONS AS THE GENERAC | | | SPECIFICATION NOTES RECOMMEND A 49" WIDTH AND THE | | | SUBMITTED PAD INFORMATION IS FOR A 46" WIDTH. | | | 2) FBC B/WPB AMENDMENTS 109.3, PLEASE PROVIDE A COST | | | BREAK DOWN OF THE VALUATION OF THE JOB. | | | 3) FBC B 107.2.5, PLEASE PROVIDE A SITE PLAN INDICATING | | | THE SET BACK MEASUREMENTS INCLUDING THE LOCATIONS OF | | | ADJACENT STRUCTURES. | | | 4) FBC B/WPB AMENDMENTS 107.1, PLEASE PROVIDE | | | VERIFFIABLE ENGINEER'S SIGNATURE AND SEAL ON GENERATOR | | | PAD ENGINEERING SHEET. |
|