| Plan Review Notes For Permit 20090915 |
| Permit Number |
20090915 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-10-16 09:55:07 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | 1- RAS 117 CALCULATIONS SUBMITTED DON'T MATCH SELECTED | | | ASSEMBLY FROM NOA 18-0919.07. SELECTED ASSEMBLY ON PAGE | | | 25 OF 27 OF NOA SUBMITTED IS FOR A SYSTEM TYPE E(4). | | | ENGINEER NEEDS TO REVISE THE SYSTEM TYPE AND THE ANCHOR | | | SPACING FOR THE FIELD AREA TO MATCH ONE SHOWN ON THE | | | NOA. ALSO, ENGINEER TO REVISE THE FASTENER SPACING FOR | | | PERIMETER AND CORNER AREAS ACCORDINGLY. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|