2020-10-16 09:55:07RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- RAS 117 CALCULATIONS SUBMITTED DON'T MATCH SELECTED
 ASSEMBLY FROM NOA 18-0919.07. SELECTED ASSEMBLY ON PAGE
 25 OF 27 OF NOA SUBMITTED IS FOR A SYSTEM TYPE E(4).
 ENGINEER NEEDS TO REVISE THE SYSTEM TYPE AND THE ANCHOR
 SPACING FOR THE FIELD AREA TO MATCH ONE SHOWN ON THE
 NOA. ALSO, ENGINEER TO REVISE THE FASTENER SPACING FOR
 PERIMETER AND CORNER AREAS ACCORDINGLY.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,