| 2020-09-28 13:54:48 | 09/28/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SHEET ONE ON FILTER EQUIPMENT SIZE IT CALLS FOR 200 |
| | SF AND YOU SPEC OUT CS 150 WHICH IS 150 SF PLEASE |
| | CLARIFY OR CHANGE TO MATCH PLANS PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 2. SHEET ONE FOR PUMP EQUIPMENT SIZE CALLS FOR A |
| | VSFHP165JEP YOU HAVE SPECS FOR A VSFHP185DV2A PLEASE |
| | CLARIFY OR CHANGE TO MATCH PLANS PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 4. THE PLANS ARE VERY BLURRY AND MOST NUMBERS CAN?T BE |
| | MADE OUT SO PLEASE SUBMIT LEGIBLE PLANS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 5. ALL PAGES NEED TO HAVE A DIGITAL SIGNATURE PER THE |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |