Plan Review Notes
Plan Review Notes For Permit 20090889
Permit Number 20090889
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-21 14:58:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION; LEVEL 2
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1. RE: PM07.01, SECTION 2.4.2.1; INDOOR GAS FITTING
 SPECIFICATION IS CALLING FOR FORGED STEEL WELD
 FITTINGS. THIS IS A 3000# SOCKET WELD FITTING
 CONFORMING TO ASTM A-105. SECTION 2.4.1 GENERAL
 SPECIFICATION INDICATES MALLEABLE FITTINGS;
 ADDITIONALLY, FBC FG 403.4.2 REQUIRES STEEL PIPE TO
 CONFORM TO ASTM A53/A53M, A106 (SEAMLESS) OR ASME
 B36.10/10M, NOT A120. PER WPB FBC 107.2.1, CLARIFY.
  
 2.RE: PM07.01, SECTION 2.4.3; SHALL BE USED FOR
 UNDERGROUND ONLY "PLASTIC PIPE SHALL NOT BE USED WITHIN
 OR UNDER ANY BUILDING OR SLAB OR BE OPERATED AT
 PRESSURES GREATER THAN 100 PSIG FOR NATURAL GAS OR 30
 PSIG TO COMPLY WITH FBC FG 404.17.1."
  
 3.RE: PLAN SHEET P01.02. THERE ARE TWO (2) EXISTING GAS
 MAIN BRANCHES SUPPLIED BY WHAT APPEARS TO BE A NATURAL
 GAS METER (CFH BASED ON 0.5 INCH WC SG 0.6). ACCORDING
 TO PREVIOUS RECORD DRAWINGS (MASTER PERMIT #01080053
 LOCATED IN CITY OF WEST PALM BEACH'S FILENET WORKPLACE,
 SEE PLAN SHEETS P-1, P-2 AND P-6, ALL REV 2 DATED
 9/18/01) PLAN P-6/DETAIL 20, THE METER IS 2LB.AND DOES
 NOT SUPPLY THE EMERGENCY GENERATOR; P-6/DETAIL 20
 INDICATES THE IN-LINE REGULATOR SHOWN ON THE BRANCH TO
 THE BAKERY IS AN MP REGULATOR AND REDUCES THE PRESSURE
 AT THAT POINT FROM POUNDS TO INCHES. THE BRANCH TO THE
 EMERGENCY GENERATOR IS IDENTIFIED AS LP GAS AND PER
 (MASTER PERMIT #01080053) PLAN P-6/DETAIL 20, PLAN P-1
 AND PLAN P-2, ALL REV 2 DATED 9/18/01, IS ACTUALLY AN
 LP SYSTEM SUPPLIED BY A 120 GALLON PROPANE TANK. PER
 WPB FBC 107.2.1, NEW DRAWINGS SUBMITTED UNDER THIS
 PERMIT 20090889 SHALL BE CONSISTENT WITH THE OLDER
 RECORD DRAWINGS AS SHOWN ON MASTER PERMIT #01080053
 PLANS. SPECIFY TYPES OF GAS, NATURAL AND LP OF EACH
 SYSTEM, SHOW EXISTING LP TANK, CONFIRM THE DELIVERY
 PRESSURE OF THE SYSTEM(S), SHOW AND IDENTIFY MP
 REGULATORS WITH POUNDS TO INCHES PRESSURE REDUCTION AND
 CONFIRM THE DISTANCE FROM THE REGULATOR(S) TO THE
 FURTHEST CONNECTED APPLIANCE/EQUIPMENT IN THE
 SYSTEM(S). LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM(S). REFER TO THE FBC FG
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4
 (37). PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED
 FOR THE APPLIANCES THAT THE DOWNSTREAM SIDE OF THE
 REGULATOR IS A SECOND SYSTEM AND ARE CONSIDERED A
 SEPARATE SYSTEM. PROVIDE THE TABLE FROM FBC FG
 APPLICABLE TO THE SIZING OF EACH SYSTEM. PROVIDE THE
 TOTAL BTUS FOR EACH SYSTEM.
  
 4.PER WPB FBC 107.2.1, PROVIDE NOTE REFERENCING
 SPECIFICATION SHEETS PM06.01 AND PM07.01, SECTION 22 40
 00 PLUMBING FOR ADDITIONAL SPECIFICATIONS
  
 5.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR NEW LRO 2G5 70
 DOUBLE RACK OVEN TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND FBC FG 402.2, AND 301.3.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED OR DIGITALLY SIGNED
 AND SEALED BY THE DESIGNER IN ACCORDANCE WITH FAC AND
 FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090889 375 S ROSEMARY AVE