| 2020-10-21 14:58:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION; LEVEL 2 |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1. RE: PM07.01, SECTION 2.4.2.1; INDOOR GAS FITTING |
| | SPECIFICATION IS CALLING FOR FORGED STEEL WELD |
| | FITTINGS. THIS IS A 3000# SOCKET WELD FITTING |
| | CONFORMING TO ASTM A-105. SECTION 2.4.1 GENERAL |
| | SPECIFICATION INDICATES MALLEABLE FITTINGS; |
| | ADDITIONALLY, FBC FG 403.4.2 REQUIRES STEEL PIPE TO |
| | CONFORM TO ASTM A53/A53M, A106 (SEAMLESS) OR ASME |
| | B36.10/10M, NOT A120. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 2.RE: PM07.01, SECTION 2.4.3; SHALL BE USED FOR |
| | UNDERGROUND ONLY "PLASTIC PIPE SHALL NOT BE USED WITHIN |
| | OR UNDER ANY BUILDING OR SLAB OR BE OPERATED AT |
| | PRESSURES GREATER THAN 100 PSIG FOR NATURAL GAS OR 30 |
| | PSIG TO COMPLY WITH FBC FG 404.17.1." |
| | |
| | 3.RE: PLAN SHEET P01.02. THERE ARE TWO (2) EXISTING GAS |
| | MAIN BRANCHES SUPPLIED BY WHAT APPEARS TO BE A NATURAL |
| | GAS METER (CFH BASED ON 0.5 INCH WC SG 0.6). ACCORDING |
| | TO PREVIOUS RECORD DRAWINGS (MASTER PERMIT #01080053 |
| | LOCATED IN CITY OF WEST PALM BEACH'S FILENET WORKPLACE, |
| | SEE PLAN SHEETS P-1, P-2 AND P-6, ALL REV 2 DATED |
| | 9/18/01) PLAN P-6/DETAIL 20, THE METER IS 2LB.AND DOES |
| | NOT SUPPLY THE EMERGENCY GENERATOR; P-6/DETAIL 20 |
| | INDICATES THE IN-LINE REGULATOR SHOWN ON THE BRANCH TO |
| | THE BAKERY IS AN MP REGULATOR AND REDUCES THE PRESSURE |
| | AT THAT POINT FROM POUNDS TO INCHES. THE BRANCH TO THE |
| | EMERGENCY GENERATOR IS IDENTIFIED AS LP GAS AND PER |
| | (MASTER PERMIT #01080053) PLAN P-6/DETAIL 20, PLAN P-1 |
| | AND PLAN P-2, ALL REV 2 DATED 9/18/01, IS ACTUALLY AN |
| | LP SYSTEM SUPPLIED BY A 120 GALLON PROPANE TANK. PER |
| | WPB FBC 107.2.1, NEW DRAWINGS SUBMITTED UNDER THIS |
| | PERMIT 20090889 SHALL BE CONSISTENT WITH THE OLDER |
| | RECORD DRAWINGS AS SHOWN ON MASTER PERMIT #01080053 |
| | PLANS. SPECIFY TYPES OF GAS, NATURAL AND LP OF EACH |
| | SYSTEM, SHOW EXISTING LP TANK, CONFIRM THE DELIVERY |
| | PRESSURE OF THE SYSTEM(S), SHOW AND IDENTIFY MP |
| | REGULATORS WITH POUNDS TO INCHES PRESSURE REDUCTION AND |
| | CONFIRM THE DISTANCE FROM THE REGULATOR(S) TO THE |
| | FURTHEST CONNECTED APPLIANCE/EQUIPMENT IN THE |
| | SYSTEM(S). LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM(S). REFER TO THE FBC FG |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 |
| | (37). PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED |
| | FOR THE APPLIANCES THAT THE DOWNSTREAM SIDE OF THE |
| | REGULATOR IS A SECOND SYSTEM AND ARE CONSIDERED A |
| | SEPARATE SYSTEM. PROVIDE THE TABLE FROM FBC FG |
| | APPLICABLE TO THE SIZING OF EACH SYSTEM. PROVIDE THE |
| | TOTAL BTUS FOR EACH SYSTEM. |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE NOTE REFERENCING |
| | SPECIFICATION SHEETS PM06.01 AND PM07.01, SECTION 22 40 |
| | 00 PLUMBING FOR ADDITIONAL SPECIFICATIONS |
| | |
| | 5.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL FOR NEW LRO 2G5 70 |
| | DOUBLE RACK OVEN TO VERIFY COMPLIANCE WITH STANDARDS |
| | NFPA 54, NFPA 58, AND FBC FG 402.2, AND 301.3. |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED OR DIGITALLY SIGNED |
| | AND SEALED BY THE DESIGNER IN ACCORDANCE WITH FAC AND |
| | FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20090889 375 S ROSEMARY AVE |