| Plan Review Notes For Permit 20090882 |
| Permit Number |
20090882 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-06 12:36:05 | TEMP CONSTRUCTION HOIST | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A LOCATION DETAIL/SITE PLAN SHOWING | | | THE LOCATION OF THE HOIST TO BE ATTACHED TO THE | | | EXISTING BUILDING NOT TO INTERFERE WITH BUILDING | | | EGRESS. | | | 2) THE MINIMUM WIND SPEED SHALL BE (170) PER FBC WPB | | | AMENDMENTS 120.1 | | | 3) ENGINEERING SHOWS ASCE 7-16 USED FOR DESIGN - SHOULD | | | BE ASCE 7-10 PER FBC CHAPTER 35 | | | |
|