Plan Review Notes
Plan Review Notes For Permit 20090880
Permit Number 20090880
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-11 10:43:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090880
 ADD: 600 S. DIXIE HWY.# 836
 CONT: JLC CUSTOM FLOORING & REMODELING
 TEL: BLANK
 E-MAIL: BLANK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV.11/2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION IS BLANK AS TO THE CONTRACTOR
 CONTRACTED TO INSTALL THE FLOORING AND UNDERLAYMENT.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 105.1
 REQUIRED.
  
 2) THE APPLICANT HAS NOT INDICATED ON THE PERMIT
 APPLICATION UNDER THE DESCRIPTION OF WORK WHAT TYPE OF
 WORK IS TO BE PREFORMED WITHIN THE SCOPE OF THIS
 PERMIT. FURTHERMORE, THERE WAS NO FLOOR PLAN AS TO
 WHERE THE WORK IS TO OCCUR. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) FOR THE FUTURE FLOOR PLAN TO BE SUBMITTED PLEASE
 NOTE THE CONTRACTOR/ QUALIFIER FOR THE COMPANY MUST
 PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER TO
 THE FLOOR PLAN.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 4) A SALES BROCHURE (PRODUCT DATA SHEET) FOR WHISPER
 MAT LVT(LUXURY VINYL TILE) WAS SUBMITTED FOR USE WITH
 LUXURY VINYL TILE. TO DATE THE CITY HAS NOT SEEN THIS
 PRODUCT WITH TESTING REPORTS.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2017 FBC-B.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  