| 2021-10-12 15:55:09 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 5TH REVIEW |
| | FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1 |
| | AMENDMENTS |
| | CITY ORDINANCES |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | NEW 4 STORY HOTEL |
| | TYPE II-B CONSTRUCTION |
| | R-1 OCCUPANCY TYPE |
| | FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88 |
| | INCLUDES 2' FREEBOARD) |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) PARTIALLY COMPLIED. THE BUILDING OFFICIAL, ROBERT |
| | BROWN, HAS CONDITIONALLY AGREED TO ACCEPT THE OPTION TO |
| | ENCLOSE THE WINDOW OPENINGS THAT EXCEED THE AMOUNT OF |
| | ALLOWABLE OPENINGS BASED ON THE FIRE SEPARATION |
| | DISTANCE TO THE RE-PLATTED PROPERTY LINE IN THE |
| | EXISTING HOTEL. THE CONDITIONS ARE THAT A HOLD WILL BE |
| | PLACED ON THE PROPOSED HOTEL'S C.O. UNTIL THE ALLOWABLE |
| | OPENINGS ISSUE IS RESOLVED AND THE PROPOSED WORK TO |
| | ENCLOSE THE WINDOW OPENINGS IS REQUIRED TO BE SHOWN ON |
| | THE REMODEL PLANS FOR THE EXISTING HOTEL LOCATED AT |
| | 1301 BELVEDERE RD. UNDER PERMIT #20120964. |
| | |
| | 4) NOT COMPLIED. [BARRIER AND MOT PLANS STILL HAVE NOT |
| | BEEN SUBMITTED.](NO PLANS FOR THIS HAVE BEEN |
| | SUBMITTED.) SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR |
| | SAFEGUARDS DURING CONSTRUCTION. SUBMIT BARRIER AND MOT |
| | PLANS. |
| | |
| | 5) PROVISO. PRODUCT APPROVALS TO BE DEFERRED. THERE IS |
| | A LIST OF PRODUCT APPROVALS TO BE DEFERRED ON SHEET |
| | A011. DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6) PROVISO. NOTED ON THE PLANS. |
| | SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR |
| | THE FOLLOWING: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | DUMPSTER ENCLOSURE |
| | SITE WALLS |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | 7) NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOFING. |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) NEW COMMENT. THE PRODUCT APPROVAL THAT WAS |
| | SUBMITTED FOR THE ROOF HATCH, NOA NO. 18-0110.05, HAS |
| | NOT BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. FBC 107. FBC 107.3.4 - PROVIDE TWO |
| | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED, |
| | HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED |
| | BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |