Plan Review Notes
Plan Review Notes For Permit 20090848
Permit Number 20090848
Review Stop B
Sequence Number 3
Notes
Date Text
2021-03-05 11:27:49PLAN
 REVIEW COMMENTS
  
 3RD REVIEW
 FBC SIXTH EDITION (2017) & CITY OF W.P.B. CHAPTER 1
 AMENDMENTS
 CITY ORDINANCES
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 NEW 4 STORY HOTEL
 TYPE II-B CONSTRUCTION
 R-1 OCCUPANCY TYPE
 FLOOD ZONE AE, BFE 12.7' NAVD88 (DFE 14.7' NAVD 88
 INCLUDES 2' FREEBOARD)
  
 NOTE: THE NUMBERING IS OFF ON THE RESPONSES STARTING AT
 NUMBER 17. THE RESPONSE FOR #17 IS ACTUALLY FOR COMMENT
 # 18 AND SO ON.
  
 1) COMPLIED.
  
 2) NOT COMPLIED. [PRECONSTRUCTION ELEVATION CERTIFICATE
 WAS NOT SUBMITTED.] (THE PERMIT CAN NOT BE ISSUED UNTIL
 A PRE-CONSTRUCTION ELEVATION CERTIFICATE HAS BEEN
 SUBMITTED AND APPROVED.) THIS PROJECT IS LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (AE FLOOD ZONE). SEE NFIP
 REVIEW COMMENTS.
  
 3) NOT COMPLIED. [SEE ENGINEERING COMMENT THAT STATES
 SITE PLAN HAS NOT BEEN APPROVED](THE PERMIT CAN NOT BE
 ISSUED UNTIL MINOR LOT SUBDIVISION HAS BEEN APPROVED.)
 THE SITE PLAN SHOWS A PROPERTY LINE THAT IS PART OF
 ANOTHER PARCEL ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S WEB SITE. PROVIDE A COPY OF THE RECORDED
 PLAT FOR THIS LOT DIVISION. FBC 107.2
  
 4) NOT COMPLIED. [THE REQUESTED DETAILED SITE PLAN
 NEEDS TO BE SUBMITTED WITH THE DOCUMENTS FOR THIS
 PERMIT.] (NO DETAILED SITE PLAN WITH REQUESTED
 INFORMATION WAS SUBMITTED. ALL ELEVATIONS ARE REQUIRED
 TO BE IN NAVD 88.) FBC 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. PROVIDE SITE PLAN WITH ELEVATIONS OF THE
 BUILDING, PARKING LOT, ACCESSIBLE PARKING, ACCESSIBLE
 ROUTES, ETC.
  
 5) NOT COMPLIED. [ENGINEERING HAS NOT APPROVED THE SITE
 PLAN.] (NO CIVIL PLANS WERE SUBMITTED.) SHOW COMPLIANCE
 WITH FBC 110.9 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY
 THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) NOT COMPLIED. [BARRIER AND MOT PLANS STILL HAVE NOT
 BEEN SUBMITTED.](NO PLANS FOR THIS HAS BEEN SUBMITTED.)
 SHOW COMPLIANCE WITH FBC CHAPTER 33 FOR SAFEGUARDS
 DURING CONSTRUCTION. SUBMIT BARRIER AND MOT PLANS.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) NOT COMPLIED. [THE REQUEST TO DEFER PRODUCT
 APPROVALS IS NOT CLEAR. THE REQUEST FOR THE PRODUCT
 APPROVALS AND OTHER ITEMS TO BE DEFERRED IS REQUIRED TO
 BE ON THE PLANS WITH THE ITEMS LISTED OR THEY WILL NEED
 TO BE SUBMITTED AND APPROVED BEFORE THE PERMIT IS
 ISSUED.] (PRODUCT APPROVALS TO BE DEFERRED. THERE IS A
 LIST OF PRODUCT APPROVALS ON SHEET A011.) THE CITY
 AMENDMENTS REQUIRES THAT PRODUCT APPROVALS ARE TO BE
 SUBMITTED FOR APPROVAL AFTER THEY HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL
 MULLIONS, STORE FRONTS, EXTERIOR DOORS, ETC. THESE
 ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY
 ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
 FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. SHOP DRAWINGS AND
 CALCULATIONS FROM DELEGATE ENGINEERS SHOULD BE INCLUDED
 ON THE LIST.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) NOT COMPLIED. [THIS IS REQUIRED TO BE ON DOCUMENTS
 FOR THIS PERMIT.] (ELEVATIONS TO BE IN NAVD 88.)
 PROVIDE THE FLOOR ELEVATIONS ON THE FLOOR PLAN OF THE
 GROUND FLOOR, THE BUILDING ELEVATIONS AND BUILDING
 SECTIONS. FBC 107.2
  
 13) PROVISO. NOTED ON THE PLANS.
 SEPARATE PERMITS, PLANS AND FEES WILL BE REQUIRED FOR
 THE FOLLOWING:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 DUMPSTER ENCLOSURE
 SITE WALLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 14) PROVISO. PRODUCT APPROVALS FOR THE ROOFING
 MATERIALS TO BE APPROVED BY THE DESIGNER OF RECORD,
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THE ROOFING PERMIT IS ISSUED. A SEPARATE SUB-
 PERMIT AND APPLICATION IS REQUIRED FOR ROOFING.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) NOT COMPLIED. [NONE OF THE REQUESTED INFORMATION
 HAS BEEN PROVIDED FOR THIS PERMIT.] (SHEET A100, THE
 SITE PLAN, REFERS TO CIVIL DRAWINGS WHICH WERE NOT
 SUBMITTED WITH THE CONSTRUCTION DOCUMENTS FOR REQUIRED
 PARKING INFORMATION. THE FINISH FLOOR ELEVATION IS
 SPECIFIED AS 15.0 BUT THE VERTICAL DATA IS NOT
 SPECIFIED. PLEASE USE NAVD 88.) PROVIDE A PARKING LOT
 PLAN THAT SHOWS THE TOTAL NUMBER OF PARKING SPACES, THE
 TOTAL NUMBER OF REQUIRED AND PROVIDED ACCESSIBLE
 SPACES, THE ACCESSIBLE VAN PARKING SPACES AND THE
 LOCATIONS OF THE ACCESSIBLE PARKING SPACES. FBC
 ACCESSIBILITY SECTIONS 208 & 502
  
 19) NOT COMPLIED. [AGAIN. THE REQUESTED INFORMATION
 NEEDS TO BE WITH THE DOCUMENTS FOR THIS PERMIT.] SHOW
 THAT THE PASSENGER LOADING ZONE COMPLIES WITH FBC
 SECTIONS 209 & 503.
  
 20) NOT COMPLIED. [ THIS NEEDS TO BE SHOWN ON THE
 DRAWINGS. TYPICALLY THE STRETCHER IS DRAWN INTO THE
 ELEVATOR ON THE PLANS WITH THE DIMENSIONS PROVIDED.]
 SHOW COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE
 AMBULANCE STRETCHER. ANY BUILDING THAT IS MORE THAN
 THREE STORIES HIGH OR IN WHICH THE VERTICAL DISTANCE
 BETWEEN THE BOTTOM TERMINAL LANDING AND THE TOP
 TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE
 CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR
 THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE
 DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR
 CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO
 ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76
 INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH
 (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN
 HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS FROM PREVIOUS REVIEW:
  
 22) COMPLIED.
  
 23) NOT COMPLIED. [SEE THE MARKUP CLOUDS AT MISSING
 PRESSURES ON PAGES 096-S200 AND 097-S201. ALSO SEE THE
 MARKUPS ON PAGE 100-S204 GRIDLINES 1 AND 6 WHICH ARE
 EXTERIOR WALL ELEVATIONS.] NEW COMMENT: SOME OF THE
 COMPONENT AND CLADDING PRESSURES AND NEGATIVE SIGNS ARE
 MISSING FROM THE ELEVATIONS ON THE STRUCTURAL DRAWINGS.
 FBC 107.2.1 & 1609
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 26 ) COMPLIED.
  
 27) NOT COMPLIED. [THE SIZE OF THE ROOF HATCH IS NOT
 SPECIFIED ON SHEETS A550 OR A011. THE RESPONSE COMMENT
 SPECIFIES A 30" X 54" ROOF ACCESS HATCH. THESE
 DIMENSIONS PROVIDE 11.25 SQFT AND DO NOT MEET THE
 REQUIRED MINIMUM SIZE OF 16 SQFT.] NEW COMMENT. I DID
 NOT SEE THAT THE SIZE OF THE ROOF HATCH IS SPECIFIED ON
 THE DRAWINGS. THE MINIMUM SIZE IS 16 SQFT WITH THE
 SMALLEST DIMENSION NOT LESS THAN 2 FT. PER
 FBC1011.12.2. IF THE ROOF HATCH IS WITHIN 10 FT OF THE
 ROOF EDGE A GUARD IS REQUIRED PER FBC1011.13 INSTALLED
 IN ACCORDANCE WITH FBC1015.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  