Plan Review Notes
Plan Review Notes For Permit 20090848
Permit Number 20090848
Review Stop P
Sequence Number 2
Notes
Date Text
2021-01-04 15:39:5801/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SECOND REQUEST, PLEASE SUBMIT A COMPLETE SET OF
 CIVIL DRAWINGS SHOWING THE WATER, SEWER, STORM
 DRAINAGE, AND GAS PIPING SYSTEMS. THE RESPONSE TO THIS
 REFERRING TO A ZONING PERMIT IS NOT ACCEPTABLE.
 REFERENCES TO THIS REVIEW ARE IMPERATIVE PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1 AND 107.3.5.1.3.
  
 2. DONE
  
 3. DONE
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 7. ON SHEET A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB
 BARS AT THE TUB'S FOOT, THE DIMENSION HAD A CLOUD OVER
 IT AND HARD TO READ. THE GRAB BAR ON THE SIDE OF THE
 1'-0 IS ON THE SAME LINE OF THE MEASUREMENT IT MAKES IT
 HARD TO READ. PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 8. DONE
  
 9. DONE
  
 10. DONE
  
 11. DONE
  
 12. DONE
  
 13. DONE
  
 14. DONE
  
 15. THE SECOND REQUEST,
  
 A. FOR SHEET A412, A414, A417, A422, A423 - IN THE
 DETAILS PERTAINING TO THE FOLLOWING SHOW THE DIMENSIONS
 REQUIRED FOR CLEAR FLOOR SPACES FOR THE HANDICAP
 ACCESSIBLE FIXTURES ON THE PLANS. COMPLY WITH
 FBC-ACCESSIBILITY CODE SECS. 604.3, 606.2. SHOW THE
 DIMENSION CLEAR FLOOR SPACE ADJACENT TO THE TUB OR
 SHOWER, LAV, AND WATER CLOSET.
  
 B. ON SHEET A410, A411, AND A416, DETAILS 13 SHOWS A
 VERTICAL GRAB BAR ON THE SHOWER AND NOT PERMITTED PER
 THE 2017 FBC ACC SEC. 609.4.
  
 C. ON SHEET A413 DETAIL 15, SHOWS A VERTICAL GRAB BAR
 ON THE SHOWER AND NOT PERMITTED PER THE 2017 FBC ACC
 SEC. 609.4.
  
 D. ON SHEET A420 AND A421, DETAILS 13, 15, AND 16 SHOW
 A VERTICAL GRAB BAR ON THE TUB AND NOT PERMITTED PER
 THE 2017 FBC ACC SEC. 609.4.
  
 16. DIMENSIONING NOT DONE
  
 17. DIMENSIONING NOT DONE
  
 18. ON SHEET A422,
  
 A. DIMENSIONING NOT DONE.
  
 B. ON DETAIL 15, GARB BARS FOR THE TUB SHOULD BE FROM
 THE TOP OF THE TUB TO THE FIRST GRAB BAR (8'-10"), AND
 THE BAK GRAB BAR IS 33" T0 36" MAX PER THE 2017 FBC
 SEC. ACC 607.4.2.
  
 C. ON DETAIL 16 LAV SHALL BE 34" TO TOP PLEASE SHOW PER
 THE 2017 FBC ACC SEC. 606.3.
  
 19. DIMENSIONING NOT DONE
  
 NOTE, PLEASE CORRECT ALL ACCESSIBILITIES PAGES TO
 COINCIDE WITH EACH OTHER, TOO MANY TO ITEMIZE. THANK
 YOU.
  
 20. DONE
  
 21. DONE
  
 22. SECOND REQUEST, SHEET A495;
  
 A. DETAIL 5; IN THE LAUNDRY ROOM, THE WASHER AND DRYER
 CLEAR FLOOR SPACE IS MISSING, AND THE DIMENSIONS ARE
 REQUIRED PER THE 2017 FBC-ACCESS. SECS. 305 SIZE.
  
 B. DETAIL 5; IN THE WOMEN'S AND MEN'S RESTROOMS ARE
 MISSING CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND LAV
 AND ALL DIMENSIONS ARE REQUIRED PER THE 2017
 FBC-ACCESS. SECS. 305 SIZE.
  
 C. DETAIL 5; IN THE DRINKING FOUNTAIN IS MISSING CLEAR
 FLOOR SPACE, AND THE DIMENSIONS ARE REQUIRED PER THE
 2017 FBC-ACCESS. SECS. 305 SIZE.
  
 D. DETAIL 2; IN THE QQ ACCESS BATHROOM, THERE IS NO
 CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND ALL
 DIMENSIONS ARE REQUIRED FOR TUB LAV AND TURNING RADIUS
 PER THE 2017 FBC-ACCESS. SECS. 305 SIZE.
  
 E. DETAILS 2, 3, AND 4 SHOW ICE BIN. PLEASE SHOW CLEAR
 FLOOR SPACE AND DIMENSIONS PER THE 2017 FBC-ACCESS.
 SECS. 305 SIZE. PLEASE PROVIDE DETAILS OF THE BIN THAT
 COMPLIES WITH REACHABILITY OFF THE DOOR PER THE 2017
 FBC ACC SEC. 308.
  
 23. COULD NOT FIND A FIRE STOP FROM THE ARCHITECT, SO
 PLEASE PROVIDE ALL DETAILS OF ALL THE COMPLETE ASSEMBLY
 ON UL 449 AND UL 605 SYSTEMS PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 24. DONE
  
 25. DONE
  
 26. WHICH PAGE OF NOTES, 7.
  
 A LINT INTERCEPTOR IS REQUIRED ON THE WASHING MACHINES
 IN THE GUEST AND STAFF LAUNDRY FACILITIES PER THE 2017
 FBC-PLUMBING SEC. P1003..6.
  
 27. DONE
  
 28. ON SHEET P201,
  
 A. PLEASE PLACE TAGS ON ALL THE RISERS (SANITARY UP) TO
 COINCIDE WITH RISERS ON ISOMETRIC DRAWING IN OTHER
 PAGES FOR THE CONTINUATION PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON-GRID E/8, THE THREE-INCH PARTIAL PIPES NEED TO BE
 LABELED TO WHERE THE CONTINUATION WILL BE. THE LAST
 COMMENT RESPONSE SAYS, ?PIPE INDICATES THE LOCATION OF
 THE DOWNSPOUT FROM PORTE-COCHERE ROOF GUTTER. PIPE WILL
 CONNECT TO STORM WATER PER CIVIL PLANS. SEE CIVIL PLANS
 FOR ADDITIONAL INFORMATION? PLEASE NOTE IT ON THE
 SECTION OF PIPE PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THERE IS NO SANITARY CONNECTION FOR THIS BATHROOM
 GROUP IN GRID 10-11 AND C-D FOR UNIT 114. PLEASE
 CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE IS 4" SANITARY UP IN THE MIDDLE OF THE LOBBY
 GREAT ROOM THAT IS NOT IN A WALL AND THE CENTER OF THE
 ROOM. PLEASE MOVE TO A WALL PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE ELEVATORS HAVE INDIRECT WASTE. PLEASE PROVIDE A
 DETAIL PER THE 2017 FBC SEC. P 1113.
  
 F. PLEASE MOVE THE ELEVATOR INDIRECT WASTE PIPE TO THE
 STORAGE ROOM, SIZE, AND SHOW ON P801 PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 29. ON SHEET P805;
  
 A. PLEASE PROVIDE THE GPM AND ROOF AREA IN FEET OF
 COVERED AREA FOR EACH RAIN LEADER STORM WATER RISER
 DIAGRAM FOR THE 2017 FBC SEC CALCULATIONS. P1106.
  
 B. PLEASE SHOW THE SLOPE OF ALL HORIZONTAL PIPE PER THE
 WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 SHOW THE HORIZONTAL PIPE SLOPE ON THE PLANS AND THE
 PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE
 SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING
 SEC.1106. THE PARAPET WALL SHALL BE INCLUDED IN THE
 STORM DRAINAGE SYSTEM'S SIZING IN ACCORDANCE WITH
 SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL
 BE CALCULATED IN ACCORDANCE WITH SEC.1105.
  
 30. DONE
  
 31. ON SHEET P201, P202, P203, P204, P301, P302, P303,
 AND P304, GRID 5-7, 15, 19 WHERE CHANGE AND NOT IN
 ORDER, ALSO D WAS MOVED UP TO FOLLOW A-8. PLEASE
 CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT A SHEET FOR THE CIVIL DRAWING IS
 REQUIRED ON THIS SET OF PLANS SUBMITTED IN COMMENT ONE.
  
 32. DONE
  
 33. DONE
  
 34.DONE
  
 35. DONE
  
 36. DONE
  
 37. THE SECOND REQUEST, PLEASE PLACE RISER TAGS ON THE
 WATER RISER AS ON P201 FOR THE EARLIER COMMENT; ALL
 RISERS ON P801, P802, P803, AND P804 SHALL MATCH THE
 FLAT CROSS-REFERENCE AND CONTINUATION. PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES, AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR IT IS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.
  
 38.DONE
  
 39. DONE
  
 40. DONE
  
 41. ON SHEET P801,
  
 A. PLEASE SHOW P-TRAPS ON LAVATORIES, TUBS, AND SHOWERS
 ON ALL RISERS PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. PLEASE SHOW THE CONTINUATION POINTS OF ALL PARTIAL
 PIPING SECTIONS SHOWN ON BOTH RISER DIAGRAMS PER THE
 WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE ARE MANY FITTING ON THE ISOMETRIC SHOWN IN THE
 WITH NO FLOW DIRECTION. PLEASE NOTE THAT SANITARY
 FITTINGS ON ALL ISOMETRIC DRAWINGS SHALL BE INSTALLED
 TO GUIDE SEWAGE AND WASTE IN THE DIRECTION OF FLOW PER
 THE 2017 FBC SECTION 706.3 INSTALLATION OF FITTINGS.
  
 D. THERE ARE CROSS TEE FITTINGS ON THE BRANCHES TO THE
 UNIT, AND ALL CONNECTIONS AND CHANGES IN DIRECTION OF
 THE SANITARY DRAINAGE SYSTEM SHALL BE MADE WITH
 APPROVED DRAINAGE FITTINGS PER THE 2017 FBC SEC. P
 706.1 1 CONNECTIONS AND CHANGES IN DIRECTION.
  
 42. ON SHEETS P802,
 A. SECOND REQUEST, PLEASE SIZE ALL SECTIONS OF WASTE
 AND SENT THE SYSTEM ON ALL THE SANITARY RISERS PER THE
 2017 FBC TABLE 710.1. (1) AND WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNIT 114 IS NOT CONNECTED TO THE 6? LINE AS NOTED ON
 P201 AS WELL; PLEASE RE-SIZE IF NEEDED AND CORRECT PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 C. FLOOR DRAIN IN LAUNDRY ROOM NOT CONNECTED TO ITS
 FEED AND NEED TO SHOW P-TRAP PER THE WPB FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THE TAGS THAT REFER TO 801 AND 801 NEED TO BE SHOWN
 ON P 201 TO REFERENCING EACH OTHER PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. PLEASE LABEL AND PIPE THAT IS BRANCHING OFF THE MAIN
 TRUNK LINE TO ITS CONTINUATION POINT PER THE WPB FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 43. DONE
  
 44. ON SHEET P802, THE SECOND REQUEST, THERE ARE
 SECTIONS OF PIPE MISSING ON THE SANITARY RISER DIAGRAM.
 PLEASE REFER TO COMMENT 28 FOR SECTION MISS, AND PLEASE
 REVISE THE DRAWING PER THE WPB FBC 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 45. ON SHEET P803 & P804 - HOSE BIBBS SHALL BE
 SEPARATELY VALVES PER FBC-PLUMBING SEC.606.2 (2) THERE
 IS A NOTE ON 803, BUT 804 HAS NO NOTE, PLEASE SHOW
 VALVE ON ISOMETRIC AND TO WHICH PAGE OF THE DETAIL IS
 THE HB-1 LOCATED PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 46. DONE
  
 47. DONE
  
 48. THE SERVICE SINKS HAVE BEEN MOVED AND NOTED, BUT
 THE SERVICE SINK (MOP SINK) SURROUNDING WALLS SHALL BE
 NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE 2017 FBC
 BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P 310.3.
 PLEASE MAKE A NOTE ON THIS SHEET.
  
 49. ON SHEET P803 & P804 - DOWN FEED RISERS SHALL BE
 EQUIPPED WITH FULLY OPEN SHUTOFF VALVES PER
 FBC-PLUMBING SEC.606.1 (5). THE RESPONSE REFERS TO AN
 AIR VENT THAT WAS NOT FOUND ON P601; PLEASE ADD VALVES
 TO ISOMETRIC OR ANNOTATE FOR FIELD CLARITY PER THE WPB
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 50. DONE
  
 51. DONE AS A NOTE
  
 52. DONE BUT REQUIRES DETAIL AS REQUESTED IN A PREVIOUS
 COMMENT.
  
 53. DONE
  
 54. THE GREASER INTERCEPTOR REQUIRES A ZONING REVIEW,
 AND AS REQUESTED IN THE PREVIOUS COMMENT, A CIVIL PLAN
 WAS ASKED FOR A REVIEW. CONTACT THE CITY'S ENGINEERING
 DEPT, AT 561-494-1040 FOR FURTHER INFORMATION ON
 STANDARD DRAWING GC-7.
  
 55. DONE
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  