| 2021-01-04 15:39:58 | 01/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SECOND REQUEST, PLEASE SUBMIT A COMPLETE SET OF |
| | CIVIL DRAWINGS SHOWING THE WATER, SEWER, STORM |
| | DRAINAGE, AND GAS PIPING SYSTEMS. THE RESPONSE TO THIS |
| | REFERRING TO A ZONING PERMIT IS NOT ACCEPTABLE. |
| | REFERENCES TO THIS REVIEW ARE IMPERATIVE PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1 AND 107.3.5.1.3. |
| | |
| | 2. DONE |
| | |
| | 3. DONE |
| | |
| | 4. DONE |
| | |
| | 5. DONE |
| | |
| | 6. DONE |
| | |
| | 7. ON SHEET A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB |
| | BARS AT THE TUB'S FOOT, THE DIMENSION HAD A CLOUD OVER |
| | IT AND HARD TO READ. THE GRAB BAR ON THE SIDE OF THE |
| | 1'-0 IS ON THE SAME LINE OF THE MEASUREMENT IT MAKES IT |
| | HARD TO READ. PLEASE CORRECT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 8. DONE |
| | |
| | 9. DONE |
| | |
| | 10. DONE |
| | |
| | 11. DONE |
| | |
| | 12. DONE |
| | |
| | 13. DONE |
| | |
| | 14. DONE |
| | |
| | 15. THE SECOND REQUEST, |
| | |
| | A. FOR SHEET A412, A414, A417, A422, A423 - IN THE |
| | DETAILS PERTAINING TO THE FOLLOWING SHOW THE DIMENSIONS |
| | REQUIRED FOR CLEAR FLOOR SPACES FOR THE HANDICAP |
| | ACCESSIBLE FIXTURES ON THE PLANS. COMPLY WITH |
| | FBC-ACCESSIBILITY CODE SECS. 604.3, 606.2. SHOW THE |
| | DIMENSION CLEAR FLOOR SPACE ADJACENT TO THE TUB OR |
| | SHOWER, LAV, AND WATER CLOSET. |
| | |
| | B. ON SHEET A410, A411, AND A416, DETAILS 13 SHOWS A |
| | VERTICAL GRAB BAR ON THE SHOWER AND NOT PERMITTED PER |
| | THE 2017 FBC ACC SEC. 609.4. |
| | |
| | C. ON SHEET A413 DETAIL 15, SHOWS A VERTICAL GRAB BAR |
| | ON THE SHOWER AND NOT PERMITTED PER THE 2017 FBC ACC |
| | SEC. 609.4. |
| | |
| | D. ON SHEET A420 AND A421, DETAILS 13, 15, AND 16 SHOW |
| | A VERTICAL GRAB BAR ON THE TUB AND NOT PERMITTED PER |
| | THE 2017 FBC ACC SEC. 609.4. |
| | |
| | 16. DIMENSIONING NOT DONE |
| | |
| | 17. DIMENSIONING NOT DONE |
| | |
| | 18. ON SHEET A422, |
| | |
| | A. DIMENSIONING NOT DONE. |
| | |
| | B. ON DETAIL 15, GARB BARS FOR THE TUB SHOULD BE FROM |
| | THE TOP OF THE TUB TO THE FIRST GRAB BAR (8'-10"), AND |
| | THE BAK GRAB BAR IS 33" T0 36" MAX PER THE 2017 FBC |
| | SEC. ACC 607.4.2. |
| | |
| | C. ON DETAIL 16 LAV SHALL BE 34" TO TOP PLEASE SHOW PER |
| | THE 2017 FBC ACC SEC. 606.3. |
| | |
| | 19. DIMENSIONING NOT DONE |
| | |
| | NOTE, PLEASE CORRECT ALL ACCESSIBILITIES PAGES TO |
| | COINCIDE WITH EACH OTHER, TOO MANY TO ITEMIZE. THANK |
| | YOU. |
| | |
| | 20. DONE |
| | |
| | 21. DONE |
| | |
| | 22. SECOND REQUEST, SHEET A495; |
| | |
| | A. DETAIL 5; IN THE LAUNDRY ROOM, THE WASHER AND DRYER |
| | CLEAR FLOOR SPACE IS MISSING, AND THE DIMENSIONS ARE |
| | REQUIRED PER THE 2017 FBC-ACCESS. SECS. 305 SIZE. |
| | |
| | B. DETAIL 5; IN THE WOMEN'S AND MEN'S RESTROOMS ARE |
| | MISSING CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND LAV |
| | AND ALL DIMENSIONS ARE REQUIRED PER THE 2017 |
| | FBC-ACCESS. SECS. 305 SIZE. |
| | |
| | C. DETAIL 5; IN THE DRINKING FOUNTAIN IS MISSING CLEAR |
| | FLOOR SPACE, AND THE DIMENSIONS ARE REQUIRED PER THE |
| | 2017 FBC-ACCESS. SECS. 305 SIZE. |
| | |
| | D. DETAIL 2; IN THE QQ ACCESS BATHROOM, THERE IS NO |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSET, AND ALL |
| | DIMENSIONS ARE REQUIRED FOR TUB LAV AND TURNING RADIUS |
| | PER THE 2017 FBC-ACCESS. SECS. 305 SIZE. |
| | |
| | E. DETAILS 2, 3, AND 4 SHOW ICE BIN. PLEASE SHOW CLEAR |
| | FLOOR SPACE AND DIMENSIONS PER THE 2017 FBC-ACCESS. |
| | SECS. 305 SIZE. PLEASE PROVIDE DETAILS OF THE BIN THAT |
| | COMPLIES WITH REACHABILITY OFF THE DOOR PER THE 2017 |
| | FBC ACC SEC. 308. |
| | |
| | 23. COULD NOT FIND A FIRE STOP FROM THE ARCHITECT, SO |
| | PLEASE PROVIDE ALL DETAILS OF ALL THE COMPLETE ASSEMBLY |
| | ON UL 449 AND UL 605 SYSTEMS PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 24. DONE |
| | |
| | 25. DONE |
| | |
| | 26. WHICH PAGE OF NOTES, 7. |
| | |
| | A LINT INTERCEPTOR IS REQUIRED ON THE WASHING MACHINES |
| | IN THE GUEST AND STAFF LAUNDRY FACILITIES PER THE 2017 |
| | FBC-PLUMBING SEC. P1003..6. |
| | |
| | 27. DONE |
| | |
| | 28. ON SHEET P201, |
| | |
| | A. PLEASE PLACE TAGS ON ALL THE RISERS (SANITARY UP) TO |
| | COINCIDE WITH RISERS ON ISOMETRIC DRAWING IN OTHER |
| | PAGES FOR THE CONTINUATION PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON-GRID E/8, THE THREE-INCH PARTIAL PIPES NEED TO BE |
| | LABELED TO WHERE THE CONTINUATION WILL BE. THE LAST |
| | COMMENT RESPONSE SAYS, ?PIPE INDICATES THE LOCATION OF |
| | THE DOWNSPOUT FROM PORTE-COCHERE ROOF GUTTER. PIPE WILL |
| | CONNECT TO STORM WATER PER CIVIL PLANS. SEE CIVIL PLANS |
| | FOR ADDITIONAL INFORMATION? PLEASE NOTE IT ON THE |
| | SECTION OF PIPE PER THE WPB FBC 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. THERE IS NO SANITARY CONNECTION FOR THIS BATHROOM |
| | GROUP IN GRID 10-11 AND C-D FOR UNIT 114. PLEASE |
| | CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. THERE IS 4" SANITARY UP IN THE MIDDLE OF THE LOBBY |
| | GREAT ROOM THAT IS NOT IN A WALL AND THE CENTER OF THE |
| | ROOM. PLEASE MOVE TO A WALL PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. THE ELEVATORS HAVE INDIRECT WASTE. PLEASE PROVIDE A |
| | DETAIL PER THE 2017 FBC SEC. P 1113. |
| | |
| | F. PLEASE MOVE THE ELEVATOR INDIRECT WASTE PIPE TO THE |
| | STORAGE ROOM, SIZE, AND SHOW ON P801 PER THE WPB FBC |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 29. ON SHEET P805; |
| | |
| | A. PLEASE PROVIDE THE GPM AND ROOF AREA IN FEET OF |
| | COVERED AREA FOR EACH RAIN LEADER STORM WATER RISER |
| | DIAGRAM FOR THE 2017 FBC SEC CALCULATIONS. P1106. |
| | |
| | B. PLEASE SHOW THE SLOPE OF ALL HORIZONTAL PIPE PER THE |
| | WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | SHOW THE HORIZONTAL PIPE SLOPE ON THE PLANS AND THE |
| | PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE |
| | SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING |
| | SEC.1106. THE PARAPET WALL SHALL BE INCLUDED IN THE |
| | STORM DRAINAGE SYSTEM'S SIZING IN ACCORDANCE WITH |
| | SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL |
| | BE CALCULATED IN ACCORDANCE WITH SEC.1105. |
| | |
| | 30. DONE |
| | |
| | 31. ON SHEET P201, P202, P203, P204, P301, P302, P303, |
| | AND P304, GRID 5-7, 15, 19 WHERE CHANGE AND NOT IN |
| | ORDER, ALSO D WAS MOVED UP TO FOLLOW A-8. PLEASE |
| | CORRECT FOR ALL PAGES PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | PLEASE NOTE THAT A SHEET FOR THE CIVIL DRAWING IS |
| | REQUIRED ON THIS SET OF PLANS SUBMITTED IN COMMENT ONE. |
| | |
| | 32. DONE |
| | |
| | 33. DONE |
| | |
| | 34.DONE |
| | |
| | 35. DONE |
| | |
| | 36. DONE |
| | |
| | 37. THE SECOND REQUEST, PLEASE PLACE RISER TAGS ON THE |
| | WATER RISER AS ON P201 FOR THE EARLIER COMMENT; ALL |
| | RISERS ON P801, P802, P803, AND P804 SHALL MATCH THE |
| | FLAT CROSS-REFERENCE AND CONTINUATION. PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES, AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" |
| | OR IT IS EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| | SPECIFIC INFORMATION. |
| | |
| | 38.DONE |
| | |
| | 39. DONE |
| | |
| | 40. DONE |
| | |
| | 41. ON SHEET P801, |
| | |
| | A. PLEASE SHOW P-TRAPS ON LAVATORIES, TUBS, AND SHOWERS |
| | ON ALL RISERS PER THE WPB FBC 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. PLEASE SHOW THE CONTINUATION POINTS OF ALL PARTIAL |
| | PIPING SECTIONS SHOWN ON BOTH RISER DIAGRAMS PER THE |
| | WPB FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. THERE ARE MANY FITTING ON THE ISOMETRIC SHOWN IN THE |
| | WITH NO FLOW DIRECTION. PLEASE NOTE THAT SANITARY |
| | FITTINGS ON ALL ISOMETRIC DRAWINGS SHALL BE INSTALLED |
| | TO GUIDE SEWAGE AND WASTE IN THE DIRECTION OF FLOW PER |
| | THE 2017 FBC SECTION 706.3 INSTALLATION OF FITTINGS. |
| | |
| | D. THERE ARE CROSS TEE FITTINGS ON THE BRANCHES TO THE |
| | UNIT, AND ALL CONNECTIONS AND CHANGES IN DIRECTION OF |
| | THE SANITARY DRAINAGE SYSTEM SHALL BE MADE WITH |
| | APPROVED DRAINAGE FITTINGS PER THE 2017 FBC SEC. P |
| | 706.1 1 CONNECTIONS AND CHANGES IN DIRECTION. |
| | |
| | 42. ON SHEETS P802, |
| | A. SECOND REQUEST, PLEASE SIZE ALL SECTIONS OF WASTE |
| | AND SENT THE SYSTEM ON ALL THE SANITARY RISERS PER THE |
| | 2017 FBC TABLE 710.1. (1) AND WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. UNIT 114 IS NOT CONNECTED TO THE 6? LINE AS NOTED ON |
| | P201 AS WELL; PLEASE RE-SIZE IF NEEDED AND CORRECT PER |
| | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | C. FLOOR DRAIN IN LAUNDRY ROOM NOT CONNECTED TO ITS |
| | FEED AND NEED TO SHOW P-TRAP PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. THE TAGS THAT REFER TO 801 AND 801 NEED TO BE SHOWN |
| | ON P 201 TO REFERENCING EACH OTHER PER THE WPB FBC |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. PLEASE LABEL AND PIPE THAT IS BRANCHING OFF THE MAIN |
| | TRUNK LINE TO ITS CONTINUATION POINT PER THE WPB FBC |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 43. DONE |
| | |
| | 44. ON SHEET P802, THE SECOND REQUEST, THERE ARE |
| | SECTIONS OF PIPE MISSING ON THE SANITARY RISER DIAGRAM. |
| | PLEASE REFER TO COMMENT 28 FOR SECTION MISS, AND PLEASE |
| | REVISE THE DRAWING PER THE WPB FBC 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 45. ON SHEET P803 & P804 - HOSE BIBBS SHALL BE |
| | SEPARATELY VALVES PER FBC-PLUMBING SEC.606.2 (2) THERE |
| | IS A NOTE ON 803, BUT 804 HAS NO NOTE, PLEASE SHOW |
| | VALVE ON ISOMETRIC AND TO WHICH PAGE OF THE DETAIL IS |
| | THE HB-1 LOCATED PER THE WPB FBC 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 46. DONE |
| | |
| | 47. DONE |
| | |
| | 48. THE SERVICE SINKS HAVE BEEN MOVED AND NOTED, BUT |
| | THE SERVICE SINK (MOP SINK) SURROUNDING WALLS SHALL BE |
| | NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE 2017 FBC |
| | BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P 310.3. |
| | PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | 49. ON SHEET P803 & P804 - DOWN FEED RISERS SHALL BE |
| | EQUIPPED WITH FULLY OPEN SHUTOFF VALVES PER |
| | FBC-PLUMBING SEC.606.1 (5). THE RESPONSE REFERS TO AN |
| | AIR VENT THAT WAS NOT FOUND ON P601; PLEASE ADD VALVES |
| | TO ISOMETRIC OR ANNOTATE FOR FIELD CLARITY PER THE WPB |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 50. DONE |
| | |
| | 51. DONE AS A NOTE |
| | |
| | 52. DONE BUT REQUIRES DETAIL AS REQUESTED IN A PREVIOUS |
| | COMMENT. |
| | |
| | 53. DONE |
| | |
| | 54. THE GREASER INTERCEPTOR REQUIRES A ZONING REVIEW, |
| | AND AS REQUESTED IN THE PREVIOUS COMMENT, A CIVIL PLAN |
| | WAS ASKED FOR A REVIEW. CONTACT THE CITY'S ENGINEERING |
| | DEPT, AT 561-494-1040 FOR FURTHER INFORMATION ON |
| | STANDARD DRAWING GC-7. |
| | |
| | 55. DONE |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |