| Date |
Text |
| 2021-01-04 17:50:48 | 01/04/20 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SHOW ON AN ISOMETRIC DRAWING THAT CLEARLY |
| | SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 |
| | FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-R |
| | SEC. G2413.4.1, G2413.4.2. |
| | |
| | 2. DONE |
| | |
| | 3. PLEASE SHOW THE TYPE OF PIPE MATERIAL BEING |
| | INSTALLED ON THE ISOMETRIC AND LABEL IT NATURAL PER THE |
| | WPB AMENDMENTS TO FBC SEC. 107.2.1. PLEASE NOTE THAT |
| | PAGE P002 HAS THE LEFT SIDE CUT OFF, SO SQUARE ON THE |
| | PAGE. |
| | |
| | 4. DONE |
| | |
| | 5. PLEASE SHOW THE ISOMETRIC THE TOTAL DISTANCE FROM |
| | THE POINT OF DELIVERY (GAS METER / MP REGULATOR / LP |
| | TANK) TO THE MOST REMOTE OUTLET IN THE BUILDING AND |
| | SYSTEM PER THE 2017 FBC-FUEL GAS SEC. 402.4.1, 402.4.2. |
| | |
| | 6. DONE |
| | |
| | 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE |
| | SYSTEM ON THE ISOMETRIC PER THE WPB FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. PLEASE SHOW THIS INFORMATION ON PAGE ISOMETRIC |
| | "DEDICATED EXHAUST LINES TERMINATING OUT THE PLAN WEST |
| | SIDE OF THE BUILDING, PROVIDED BY THE MANUFACTURER." |
| | |
| | 9. DONE |
| | |
| | 10. PLEASE PLACE A NOTE ON THE ISOMETRIC DRAWINGS |
| | SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| | OTHER STANDARD WAS USED TO DESIGN THIS GAS SYSTEM. |
| | REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, |
| | 402.3, AND TABLES 402.4 (1) THRU 402.4 (37). |
| | |
| | 11. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE AND SHOW REGULATORS PER THE |
| | 2017 FBC FG SEC 410.2. |
| | |
| | 12. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS |
| | ISOMERIC PER THE 2017 FBC FG SEC. 409.4 OR 2017 FBC |
| | RES. SEC. G2401.1.3. |
| | |
| | 13. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT |
| | INSTALLED PER THE 2017 FBC FG 408.2. |
| | |
| | 14. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS |
| | SYSTEM TO BE PURGE AND ADMINISTERED BY A CITY |
| | INSPECTOR. BEFORE DOING THIS PROCESS, PLEASE DESCRIBE |
| | HOW THE PURGE WILL OCCUR AND WHEN SUBMITTED TO THE |
| | CHIEF PLUMBING INSPECTOR IN ADVANCE. PLEASE CALL |
| | 561-805-6692 FOR FURTHER CLARIFICATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |