Plan Review Notes
Plan Review Notes For Permit 20090848
Permit Number 20090848
Review Stop E
Sequence Number 2
Notes
Date Text
2020-12-21 08:37:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ALL COMMENTS HAVE BEEN ADDRESSED BUT I NEED SOME
 CLEARIFICATION ON THE FIRE PUMP PANEL. A SINGLE
 DISCONNECTING DEVICE IS ALLOWED FOR FIRE PUMP CIRCUITS
 EM PANEL AND THEN TO THE FIRE PUMP PANEL?
  
 (1) NUMBER OF DISCONNECTING MEANS.
 (A) GENERAL. A SINGLE DISCONNECTI NG MEANS AND
 ASSOCIATED OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE
 PERMITTED TO BE INSTALLED BETWEEN THE FIRE PUMP POWER
 SOURCE(S) AND ONE OF THE FOLLOWING: [20:9.1.2]
 (1) A LISTED FIRE PUMP CONTROLLER (2) A LISTED FIRE
 PUMP POWER TRANSFER SWITCH (3) A LISTED COMBINATION
 FIRE PUMP CONTROLLER AND P OWER TRANSFER SWITCH