| Plan Review Notes For Permit 20090848 |
| Permit Number |
20090848 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-12-21 08:37:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ALL COMMENTS HAVE BEEN ADDRESSED BUT I NEED SOME | | | CLEARIFICATION ON THE FIRE PUMP PANEL. A SINGLE | | | DISCONNECTING DEVICE IS ALLOWED FOR FIRE PUMP CIRCUITS | | | EM PANEL AND THEN TO THE FIRE PUMP PANEL? | | | | | | (1) NUMBER OF DISCONNECTING MEANS. | | | (A) GENERAL. A SINGLE DISCONNECTI NG MEANS AND | | | ASSOCIATED OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE | | | PERMITTED TO BE INSTALLED BETWEEN THE FIRE PUMP POWER | | | SOURCE(S) AND ONE OF THE FOLLOWING: [20:9.1.2] | | | (1) A LISTED FIRE PUMP CONTROLLER (2) A LISTED FIRE | | | PUMP POWER TRANSFER SWITCH (3) A LISTED COMBINATION | | | FIRE PUMP CONTROLLER AND P OWER TRANSFER SWITCH |
|