| 2020-11-01 07:33:54 | 1) SUBMIT A COMPLETE SET OF CIVIL DRAWINGS SHOWING THE |
| | WATER, SEWER, STORM DRAINAGE AND GAS PIPING SYSTEMS. |
| | WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 2) SHT. A030 - CHAPTER 11 - ACCESSIBILITY NOTES - THERE |
| | IS A NOTE ON THE BOTTOM LEFT COLUMN THAT REFERS TO |
| | FLORIDA ACCESSIBILITY CODE SECTION 213.2 , EXCEPTION |
| | #2. THIS EXCEPTION REFERS TO HISTORIC BUILDINGS AND HAS |
| | NOTHING TO DO WITH THIS PROJECT. DELETE THIS FROM THE |
| | PLAN.THE NOTE ALSO REFERS TO SECTION 1107. SECTION 1107 |
| | IN THE FBC-BUILDING IS NOTED AS "RESERVED" SO THIS IS |
| | ALSO NOT APPLICABLE.REMOVE THIS NOTE FROM THE PLAN. |
| | 3) SHT. A400 - THE GRAB BARS SHALL BE MEASURED TO THE |
| | TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE. |
| | FBC-ACCESS. SEC. 609.4. |
| | 4) THE PLANS SHOW THE INSTALLATION OF VERTICAL GRAB |
| | BARS ON SHT. A400 AND IN NUMEROUS OTHER DETAILS AND |
| | ELEVATIONS THROUGHOUT THE PLANS. SECTION 609.4 OF THE |
| | FBC-ACCESS. REQUIRES GRAB BARS TO BE INSTALLED IN THE |
| | HORIZONTAL POSITION. THERE IS NO EXCEPTION IN THE |
| | ACCESSIBILITY CODE ALLOWING FOR THE INSTALLATION OF |
| | GRAB BARS IN THE VERTICAL POSITION. DELETE THIS DETAIL |
| | FROM THE PLANS. REFER TO SHTS. A410 - A415 AMONG |
| | OTHERS. |
| | 5) SHT. A400 - BATHTUB DETAIL - SHOWS CONTROLS NEXT TO |
| | THE TUB SPOUT AND ALSO A SET OF SHOWER CONTROLS. |
| | CLARIFY. THE CONTROLS SHALL BE LOCATED PER FBC-ACCESS. |
| | SEC. 607..5. |
| | 6) SHT. A400 - BATHTUB DETAIL -THE REMOVABLE TUB SEAT |
| | SHALL COMPLY WITH FBC-ACCESS. SEC.610.2 AND FIGURE |
| | 610.2. SHOW COMPLIANCE ON THE PLAN. |
| | 7) SHT. A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB |
| | BARS AT THE HEAD AND FOOT OF THE TUB SHALL BE LOCATED |
| | AT THE FRONT EDGE OF THE TUB BUT THE DETAIL SHOWS THE |
| | GRAB BARS SET BACK 4 INCHES FROM THE EDGE OF THE TUB. |
| | COMPLY WITH FBC-ACCESS. SEC. 607.4.2.2 & 607.4.2.3. |
| | 8) SHT.A400 - HOUSEKEEPING/EVS CLOSET DETAIL - CLARIFY |
| | THE TYPE OF WALL SURFACE TO BE INSTALLED AROUND THE |
| | SERVICE SINKS. SECTION 1210.2.2. OF THE FBC-BUILDING |
| | REQUIRES WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE |
| | SINKS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO |
| | A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR AND |
| | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. EPOXY PAINT |
| | DOES MEET THE REQUIREMENTS OF THIS SECTION. |
| | 9) SHT. A400 - TOILET/WATER CLOSETS DETAIL - SHOW THE |
| | MINIMUM HEIGHT OF THE TOILET PAPER DISPENSER. COMPLY |
| | WITH FBC-ACCCESS. SEC.604.7. |
| | 10) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE |
| | DRINKING FOUNTAINS AS REQUIRED BY FBC-ACCESS. SECS.305 |
| | & 602.2. |
| | 11) SHT. A400 - DRIINKING FOUNTAIN DETAIL - SHOW THE |
| | REQUIRED CLEARANCE UNDER THE DRINKING FOUNTAIN. THE |
| | CLEARANCE SHALL BE FROM THE FINISH FLOOR TO THE BOTTOM |
| | OF THE UNIT, NOT TO THE BOTTOM OFF THE BASIN. COMPLY |
| | WITH FBC-ACCESS. FOR KNEE AND TOE CLEARANCE. |
| | 12) SHT. A400 - ACCESSIBLE TRANSFER SHOWER DETAIL - |
| | SHOW THE HEIGHT OF THE SHOWER CONTROLS ON THE PLAN TO |
| | THE CENTERLINE OF THE HANDLE. COMPLY WITH FBC-ACCESS. |
| | SEC. 608.5.1 & FIGURE 608.5.1. |
| | 13) SHT. A400 - SUBMIT DETAILS ON THE TRANSFER SHOWER |
| | SEAT.THE SEAT SHALL COMPLY WITH FBC-ACCESS. SECS. |
| | 610.3, 610.3.2. |
| | 14) SHT. A400 - ROLL IN SHOWER DETAIL - SUBMIT DETAILS |
| | ON THE ROLL IN SHOWER SEAT. THE SEAT SHALL COMPLY WITH |
| | FBC-ACCESS. SEC.610.3, 610.3.1. |
| | 15) SHT. A412 - DETAIL #1 - SHOW THE DIMENSIONS OF THE |
| | REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE |
| | FIXTURES ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY |
| | CODE SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE |
| | ADJACENT TO THE SHOWER. |
| | 16) SHT. A414 - SHOW THE DIMENSIONS OF THE REQUIRED |
| | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES |
| | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE |
| | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT |
| | TO THE SHOWER. THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC. |
| | 606.2. |
| | 17) SHT. A417 - SHOW THE DIMENSIONS OF THE REQUIRED |
| | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES |
| | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE |
| | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT |
| | TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC. |
| | 606.2. |
| | 18) SHT. A422 - SHOW THE DIMENSIONS OF THE REQUIRED |
| | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES |
| | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE |
| | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT |
| | TO THE TUB. |
| | 19) SHT. A423 - SHOW THE DIMENSIONS OF THE REQUIRED |
| | CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES |
| | ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE |
| | SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT |
| | TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC. |
| | 606.2. |
| | 20) SUBMIT MANUFACTURER'S SSPECIFICATIONS FOR THE |
| | DRINKING FOUNTAIN/BOTTLE FILLER IN THE FITNESS ROOM. |
| | 21) SHT. A450 - DETAIL #8 SHOWS THE LAVATORY WITH 2 |
| | FEET OF CLEARANCE BELOW THE LAVATORY. A MINIMUM |
| | CLEARANCE OF 27 INCHES FROM THE FINISH FLOOR TO THE |
| | BOTTOM OF THE CABINET/APRONIS REQUIRED PER FBC-ACCESS. |
| | SEC. 306 FOR KNEE AND TOE CLEARANCE. |
| | 22) SHT. A450 - LAUNDRY DETAIL - THE WASHER AND DRYER |
| | SHALL COMPLY WITH FBC-ACCESS. SECS. 309, 611.2, 611.3, |
| | 611.4. SHOW COMPLIANCE ON THE PLANS. |
| | 23) SUBMIT LISTED FIRESTOPPING DETAILS FOR NONMETALLIC |
| | PIPING THROUGH RATED WALLS AND FLOORS. THE DETAIL ON |
| | SHT. A805 APPEARS TO BE ONLY FOR DRAIN CONNECTIONS TO |
| | WATER CLOSETS AND THE DETAIL ON SHT. A806 FOR RATED |
| | WALL ASSEMBLIES IS FOR NONMETALLIC PIPE WITH A DIAMETER |
| | OF 2 INCHES OR LESS. ALSO, THE DETAILS ON SHT. P601 ARE |
| | VAGUE AND UNACCEPTABLE. SUBMIT THE COMPLETE UL ASSEMBLY |
| | DETAILS FOR THE UL 449 & UL 605 SYSTEMS. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 24) SHT. P001 - INDICATE ON THE PLAN WHAT STANDARD WAS |
| | USED IN THE SIZING OF THE GREASE INTERCEPTOR. THE |
| | INTERCEPTOR SHALL BE SIZED IN THE ACCORDANCE WITH ONE |
| | OF THE STANDARDS LISTED IN FBC-PLUMBING SEC.1003.3.4. |
| | OR RULE 64E-6 OF THE FL. ADMIN. CODE. THE EQUATION ON |
| | THE PLANS APPEARS TO BE INCOMPLETE. |
| | 25) TEMPERED WATER IS REQUIRED TO THE LAVATORIES |
| | LOCATED IN PUBLIC TOILET FACILITIES. TEMPERED WATER |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B 125.3 PER FBC-PLUMBING SEC.416.5. |
| | 26) A LINT INTERCEPTOR IS REQUIRED ON THE WASHING |
| | MACHINES IN THE GUEST AND STAFF LAUNDRY FACILITIES PER |
| | FBC-PLUMBING SEC.1003..6. |
| | 27) A FLOOR DRAIN IS REQUIRED IN THE ROOM CONTAINING |
| | THE AUTOMATIC CLOTHES WASHERS PER FBC-PLUMBING |
| | SEC.412.4. THE DRAIN SHALL HAVE AN OUTLET OF NOT LESS |
| | THAN 3 INCHES. |
| | 28) SHT. P201 - PLACE RISER TAGS ON THE RISERS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 29) SUBMIT A COMPLETE STORM WATER RISER DIAGRAM. SHOW |
| | THE SLOPE OF THE HORIZONTAL PIPE ON THE PLANS AND THE |
| | PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE |
| | SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING |
| | SEC.1106. THE PARAPET WALL SHALL BE INLUDED IN THE |
| | SIZING OF THE STORM DRAINAGE SYSTEM IN ACCORDANCE WWITH |
| | SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL |
| | BE CALCULATED IN ACCORDANCE WITH SEC.1105. |
| | 30) SHT. P201 - THE PLAN NOTES "6 INCH STORM TO CLEAR |
| | WATER WASTE" WITH ARROWS POINTING TO AN AREA BUT THERE |
| | IS NO PIPING SHOWN. CLARIFY. REFER TO GRID LINES D/4-5. |
| | CLARIFY. |
| | 31) SHT. P201 - THERE IS A PARTIAL SECTION OF 3 INCH |
| | PIPE SHOWN AT GRID LINE E/8. SHOW CONTINUATION POINT |
| | AND TERMINATION POINT. |
| | 32) THE RAIN WATER LEADERS AND THE OVERFLOW DRAINS |
| | SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE |
| | STRUCTURE SIDEWALL. FBC-BUILDING SEC.1503.7. |
| | 33) SHT. P201 SHOWS A 4 INCH SANITARY LINE AT GRID |
| | LINES A.8/18.2-19 AND THE SAME LINE IS SHOWN AS 3 INCH |
| | ON SHT. P801. CLARIFY. |
| | 34) SHT. P201 - THE FLOOR DRAINS IN THE MEN'S AND |
| | WOMEN'S TOILET ROOMS ON THE FIRST FLOOR APPEAR TO |
| | EXCEED THE DISTANCE FROM A VENT PER FBC-PLUMBING TABLE |
| | 9091. |
| | 35) SHT. P203 - GENERAL NOTE #3 - SLOPE OF HORIZONTAL |
| | DRAINAGE PIPE SHALL COMPLY WITH FBC-PLUMBING SEC. 704.1 |
| | & TABLE 704.1. REVISE THE NOTE. |
| | 36) HOT WATER PIPING SHALL BE INSULATED PER FBC-ENERGY |
| | SEC. C404.4 & TABLE C403.2.10.INDICATE THE INSULATION |
| | THICKNESS FOR THE DIFFERENT PIPE SIZES ON THE PLANS. |
| | 37) PLACE RISER TAGS ON THE WATER RISER. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 38) SHT. P301 - LABEL THE 1 1/2 INCH DHR LINE FOR THE |
| | UNISEX TOILET ROOM ON THE PLANS. |
| | 39) SHT. P301 - THERE IS A SECTION OF SANITARY PIPE |
| | OVERLAYED IN THE GREAT ROOM AREA THAT DOES NOT |
| | BELONG.REVISE THE DRAWING . |
| | 40) SHT. P301 SHOWS A 4 INCH DWHR UP AND SHT. P804 |
| | SHOWS THIS LINE AS 4 INCH DCW UP. CLARIFY. |
| | 41) SHT. P801 - THERE ARE SECTIONS OF PIPE MISSING ON |
| | THE KITCHEN SINKS (KS-1) AND ALSO ON US-1 AND OTHER |
| | AREAS, TRAPS NOT SHOWN ON LAVATORIES OR SHOWERS. SHOW |
| | THE CONTINUATION POINTS OF ALL PARTIAL SECTIONS OF |
| | PIPING SHOWN ON BOTH RISER DIAGRAMS. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 42) SHT. P801 & P802 - SIZE ALL SECTIONS OF THE WASTE |
| | AND VENT SYSTEM ON ALL THE SANITARY RISERS AND SHOW THE |
| | DRAINAGE FIXTURE LOAD ON THE RISERS AND THE TOTAL |
| | DRAINAGE FIXTURE LOAD ON THE MAIN LINE. COMPLY WITH |
| | FBC-PLUMBING TABLE 710.1 (1) & TABLE 710..1 (2) . WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 43) SHT. P801 & P201 - THE FLOOR DRAINS IN THE STAFF |
| | AND GUEST LAUNDRIES AND ALSO IN THE PANTRY APPEAR TO |
| | EXCED THE DISTANCE FROM A VENT. COMPLY WITH |
| | FBC-PLUMBING TABLE 909.1. |
| | 44) SHT. P802 - THERE ARE SECTIONS OF PIPE MISSING ON |
| | THE SANITARY RISER DIAGRAM. REVISE THE DRAWING.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 45) SHTS. P803 & P804 - HOSE BIBBS SHALL BE SEPARATELY |
| | VALVED PER FBC-PLUMBING SEC.606.2 (2). |
| | 46) SHT. P803 - SHOW THE 1/2 INCH DHR LINE BY STORAGE |
| | ROOM EQ1.11 ON THE WATER RISER. |
| | 47) SHT. P804 - IDENTIFY THE WASHING MACHINE IN THE |
| | STAFF LAUNDRY ON THE WATER RISER.(EQUIPMENT ROOM EQ |
| | 1.2). |
| | 48) THE PLUMBING SHEETS SHOW SERVICE SINKS ON LEVELS 2, |
| | 3 & 4 BUT THEY ARE NOT SHOWN ON THE ARCHITECTURAL |
| | PLANS. CLARIFY. |
| | 49) SHTS. P803 & P804 - DOWNFEED RISERS SHALL BE |
| | EQUIPPED WITH FULLL OPEN SHUTOFF VALVES PER |
| | FBC-PLUMBING SEC.606.1 (5). |
| | 50) SHT. P803 - IDENTIFY THE WASHING MACHINE IN THE |
| | GUEST LAUNDRY ON THE WATER RISER. |
| | 51) SHUTOFF VALVES ARE REQUIRED AT THE BASE OF RISERS 3 |
| | INCH DHW & 4 INCH DCW |
| | 52) THE FLOOR DRAIN IN THE ELEVATOR SHAFT SHALL BE |
| | INDIRECTLY CONNETED TO THE PLUMBING SYSTEM PER |
| | FBC-PLUMBING SEC. 3301.6. |
| | 53) INDICATE ON THE PLAN IF THE ELEVATOR IS HYDRAULIC |
| | OR TRACTION TYPE. IF HYYDRAULIC, THE INSTALLATION OF |
| | THE FLOOR DRAIN IN THE PIT SHALL OMPLY WITH |
| | FBC-PLUMBING SEC.1003.4. |
| | 54) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR. THE |
| | GREASE INTERCEPTOR SHALL COMPLY WITH THE FL. ADMIN.CODE |
| | RULE 64E-6 AND THE CITY OF WEST PALM BEACH STANDARD |
| | DETAIL GS-7. CONTACT THE CITY'S ENGINEERING DEPT. AT |
| | 561-494-1040 FOR FURTHER INFORMATION ON TANDARDD |
| | DRAWING GC-7. |
| | 55) SWAY BRACING SHALL BE PROVIDED AT CHANGES IN |
| | DIRECTION GREATER THAN 45 DEGREES FOR DRAINAGE PIPE |
| | SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6. |
| | SUBMIT DETAIL. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |