Plan Review Notes
Plan Review Notes For Permit 20090848
Permit Number 20090848
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-01 07:33:541) SUBMIT A COMPLETE SET OF CIVIL DRAWINGS SHOWING THE
 WATER, SEWER, STORM DRAINAGE AND GAS PIPING SYSTEMS.
 WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 2) SHT. A030 - CHAPTER 11 - ACCESSIBILITY NOTES - THERE
 IS A NOTE ON THE BOTTOM LEFT COLUMN THAT REFERS TO
 FLORIDA ACCESSIBILITY CODE SECTION 213.2 , EXCEPTION
 #2. THIS EXCEPTION REFERS TO HISTORIC BUILDINGS AND HAS
 NOTHING TO DO WITH THIS PROJECT. DELETE THIS FROM THE
 PLAN.THE NOTE ALSO REFERS TO SECTION 1107. SECTION 1107
 IN THE FBC-BUILDING IS NOTED AS "RESERVED" SO THIS IS
 ALSO NOT APPLICABLE.REMOVE THIS NOTE FROM THE PLAN.
 3) SHT. A400 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE.
 FBC-ACCESS. SEC. 609.4.
 4) THE PLANS SHOW THE INSTALLATION OF VERTICAL GRAB
 BARS ON SHT. A400 AND IN NUMEROUS OTHER DETAILS AND
 ELEVATIONS THROUGHOUT THE PLANS. SECTION 609.4 OF THE
 FBC-ACCESS. REQUIRES GRAB BARS TO BE INSTALLED IN THE
 HORIZONTAL POSITION. THERE IS NO EXCEPTION IN THE
 ACCESSIBILITY CODE ALLOWING FOR THE INSTALLATION OF
 GRAB BARS IN THE VERTICAL POSITION. DELETE THIS DETAIL
 FROM THE PLANS. REFER TO SHTS. A410 - A415 AMONG
 OTHERS.
 5) SHT. A400 - BATHTUB DETAIL - SHOWS CONTROLS NEXT TO
 THE TUB SPOUT AND ALSO A SET OF SHOWER CONTROLS.
 CLARIFY. THE CONTROLS SHALL BE LOCATED PER FBC-ACCESS.
 SEC. 607..5.
 6) SHT. A400 - BATHTUB DETAIL -THE REMOVABLE TUB SEAT
 SHALL COMPLY WITH FBC-ACCESS. SEC.610.2 AND FIGURE
 610.2. SHOW COMPLIANCE ON THE PLAN.
 7) SHT. A400 - BATHTUB DETAIL -THE EDGE OF THE GRAB
 BARS AT THE HEAD AND FOOT OF THE TUB SHALL BE LOCATED
 AT THE FRONT EDGE OF THE TUB BUT THE DETAIL SHOWS THE
 GRAB BARS SET BACK 4 INCHES FROM THE EDGE OF THE TUB.
 COMPLY WITH FBC-ACCESS. SEC. 607.4.2.2 & 607.4.2.3.
 8) SHT.A400 - HOUSEKEEPING/EVS CLOSET DETAIL - CLARIFY
 THE TYPE OF WALL SURFACE TO BE INSTALLED AROUND THE
 SERVICE SINKS. SECTION 1210.2.2. OF THE FBC-BUILDING
 REQUIRES WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO
 A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR AND
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. EPOXY PAINT
 DOES MEET THE REQUIREMENTS OF THIS SECTION.
 9) SHT. A400 - TOILET/WATER CLOSETS DETAIL - SHOW THE
 MINIMUM HEIGHT OF THE TOILET PAPER DISPENSER. COMPLY
 WITH FBC-ACCCESS. SEC.604.7.
 10) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAINS AS REQUIRED BY FBC-ACCESS. SECS.305
 & 602.2.
 11) SHT. A400 - DRIINKING FOUNTAIN DETAIL - SHOW THE
 REQUIRED CLEARANCE UNDER THE DRINKING FOUNTAIN. THE
 CLEARANCE SHALL BE FROM THE FINISH FLOOR TO THE BOTTOM
 OF THE UNIT, NOT TO THE BOTTOM OFF THE BASIN. COMPLY
 WITH FBC-ACCESS. FOR KNEE AND TOE CLEARANCE.
 12) SHT. A400 - ACCESSIBLE TRANSFER SHOWER DETAIL -
 SHOW THE HEIGHT OF THE SHOWER CONTROLS ON THE PLAN TO
 THE CENTERLINE OF THE HANDLE. COMPLY WITH FBC-ACCESS.
 SEC. 608.5.1 & FIGURE 608.5.1.
 13) SHT. A400 - SUBMIT DETAILS ON THE TRANSFER SHOWER
 SEAT.THE SEAT SHALL COMPLY WITH FBC-ACCESS. SECS.
 610.3, 610.3.2.
 14) SHT. A400 - ROLL IN SHOWER DETAIL - SUBMIT DETAILS
 ON THE ROLL IN SHOWER SEAT. THE SEAT SHALL COMPLY WITH
 FBC-ACCESS. SEC.610.3, 610.3.1.
 15) SHT. A412 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE
 FIXTURES ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY
 CODE SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE
 ADJACENT TO THE SHOWER.
 16) SHT. A414 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE SHOWER. THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC.
 606.2.
 17) SHT. A417 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC.
 606.2.
 18) SHT. A422 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE TUB.
 19) SHT. A423 - SHOW THE DIMENSIONS OF THE REQUIRED
 CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE FIXTURES
 ON THE PLANS. COMPLY WITH FBC-ACCESSIBILITY CODE
 SECS.604.3, 606.2. SHOW THE CLEAR FLOOR SPACE ADJACENT
 TO THE TUB. THE CLEAR FLOOR SPACE FOR THE LAVATORY
 SHALL BE POSITIONED FOR A FORWARD APPROACH PER SEC.
 606.2.
 20) SUBMIT MANUFACTURER'S SSPECIFICATIONS FOR THE
 DRINKING FOUNTAIN/BOTTLE FILLER IN THE FITNESS ROOM.
 21) SHT. A450 - DETAIL #8 SHOWS THE LAVATORY WITH 2
 FEET OF CLEARANCE BELOW THE LAVATORY. A MINIMUM
 CLEARANCE OF 27 INCHES FROM THE FINISH FLOOR TO THE
 BOTTOM OF THE CABINET/APRONIS REQUIRED PER FBC-ACCESS.
 SEC. 306 FOR KNEE AND TOE CLEARANCE.
 22) SHT. A450 - LAUNDRY DETAIL - THE WASHER AND DRYER
 SHALL COMPLY WITH FBC-ACCESS. SECS. 309, 611.2, 611.3,
 611.4. SHOW COMPLIANCE ON THE PLANS.
 23) SUBMIT LISTED FIRESTOPPING DETAILS FOR NONMETALLIC
 PIPING THROUGH RATED WALLS AND FLOORS. THE DETAIL ON
 SHT. A805 APPEARS TO BE ONLY FOR DRAIN CONNECTIONS TO
 WATER CLOSETS AND THE DETAIL ON SHT. A806 FOR RATED
 WALL ASSEMBLIES IS FOR NONMETALLIC PIPE WITH A DIAMETER
 OF 2 INCHES OR LESS. ALSO, THE DETAILS ON SHT. P601 ARE
 VAGUE AND UNACCEPTABLE. SUBMIT THE COMPLETE UL ASSEMBLY
 DETAILS FOR THE UL 449 & UL 605 SYSTEMS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 24) SHT. P001 - INDICATE ON THE PLAN WHAT STANDARD WAS
 USED IN THE SIZING OF THE GREASE INTERCEPTOR. THE
 INTERCEPTOR SHALL BE SIZED IN THE ACCORDANCE WITH ONE
 OF THE STANDARDS LISTED IN FBC-PLUMBING SEC.1003.3.4.
 OR RULE 64E-6 OF THE FL. ADMIN. CODE. THE EQUATION ON
 THE PLANS APPEARS TO BE INCOMPLETE.
 25) TEMPERED WATER IS REQUIRED TO THE LAVATORIES
 LOCATED IN PUBLIC TOILET FACILITIES. TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B 125.3 PER FBC-PLUMBING SEC.416.5.
 26) A LINT INTERCEPTOR IS REQUIRED ON THE WASHING
 MACHINES IN THE GUEST AND STAFF LAUNDRY FACILITIES PER
 FBC-PLUMBING SEC.1003..6.
 27) A FLOOR DRAIN IS REQUIRED IN THE ROOM CONTAINING
 THE AUTOMATIC CLOTHES WASHERS PER FBC-PLUMBING
 SEC.412.4. THE DRAIN SHALL HAVE AN OUTLET OF NOT LESS
 THAN 3 INCHES.
 28) SHT. P201 - PLACE RISER TAGS ON THE RISERS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 29) SUBMIT A COMPLETE STORM WATER RISER DIAGRAM. SHOW
 THE SLOPE OF THE HORIZONTAL PIPE ON THE PLANS AND THE
 PIPE SIZE OF EACH SECTION OF PIPE. THE STORM DRAINAGE
 SYSTEM SHALL BE SIZED IN ACCORDANCE WITH FBC-PLUMBING
 SEC.1106. THE PARAPET WALL SHALL BE INLUDED IN THE
 SIZING OF THE STORM DRAINAGE SYSTEM IN ACCORDANCE WWITH
 SEC.1106.4. THE FLOW RATE THROUGH THE ROOF DRAIN SHALL
 BE CALCULATED IN ACCORDANCE WITH SEC.1105.
 30) SHT. P201 - THE PLAN NOTES "6 INCH STORM TO CLEAR
 WATER WASTE" WITH ARROWS POINTING TO AN AREA BUT THERE
 IS NO PIPING SHOWN. CLARIFY. REFER TO GRID LINES D/4-5.
 CLARIFY.
 31) SHT. P201 - THERE IS A PARTIAL SECTION OF 3 INCH
 PIPE SHOWN AT GRID LINE E/8. SHOW CONTINUATION POINT
 AND TERMINATION POINT.
 32) THE RAIN WATER LEADERS AND THE OVERFLOW DRAINS
 SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE
 STRUCTURE SIDEWALL. FBC-BUILDING SEC.1503.7.
 33) SHT. P201 SHOWS A 4 INCH SANITARY LINE AT GRID
 LINES A.8/18.2-19 AND THE SAME LINE IS SHOWN AS 3 INCH
 ON SHT. P801. CLARIFY.
 34) SHT. P201 - THE FLOOR DRAINS IN THE MEN'S AND
 WOMEN'S TOILET ROOMS ON THE FIRST FLOOR APPEAR TO
 EXCEED THE DISTANCE FROM A VENT PER FBC-PLUMBING TABLE
 9091.
 35) SHT. P203 - GENERAL NOTE #3 - SLOPE OF HORIZONTAL
 DRAINAGE PIPE SHALL COMPLY WITH FBC-PLUMBING SEC. 704.1
 & TABLE 704.1. REVISE THE NOTE.
 36) HOT WATER PIPING SHALL BE INSULATED PER FBC-ENERGY
 SEC. C404.4 & TABLE C403.2.10.INDICATE THE INSULATION
 THICKNESS FOR THE DIFFERENT PIPE SIZES ON THE PLANS.
 37) PLACE RISER TAGS ON THE WATER RISER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 38) SHT. P301 - LABEL THE 1 1/2 INCH DHR LINE FOR THE
 UNISEX TOILET ROOM ON THE PLANS.
 39) SHT. P301 - THERE IS A SECTION OF SANITARY PIPE
 OVERLAYED IN THE GREAT ROOM AREA THAT DOES NOT
 BELONG.REVISE THE DRAWING .
 40) SHT. P301 SHOWS A 4 INCH DWHR UP AND SHT. P804
 SHOWS THIS LINE AS 4 INCH DCW UP. CLARIFY.
 41) SHT. P801 - THERE ARE SECTIONS OF PIPE MISSING ON
 THE KITCHEN SINKS (KS-1) AND ALSO ON US-1 AND OTHER
 AREAS, TRAPS NOT SHOWN ON LAVATORIES OR SHOWERS. SHOW
 THE CONTINUATION POINTS OF ALL PARTIAL SECTIONS OF
 PIPING SHOWN ON BOTH RISER DIAGRAMS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 42) SHT. P801 & P802 - SIZE ALL SECTIONS OF THE WASTE
 AND VENT SYSTEM ON ALL THE SANITARY RISERS AND SHOW THE
 DRAINAGE FIXTURE LOAD ON THE RISERS AND THE TOTAL
 DRAINAGE FIXTURE LOAD ON THE MAIN LINE. COMPLY WITH
 FBC-PLUMBING TABLE 710.1 (1) & TABLE 710..1 (2) . WPB
 AMEND. TO FBC SEC. 107.2.1.
 43) SHT. P801 & P201 - THE FLOOR DRAINS IN THE STAFF
 AND GUEST LAUNDRIES AND ALSO IN THE PANTRY APPEAR TO
 EXCED THE DISTANCE FROM A VENT. COMPLY WITH
 FBC-PLUMBING TABLE 909.1.
 44) SHT. P802 - THERE ARE SECTIONS OF PIPE MISSING ON
 THE SANITARY RISER DIAGRAM. REVISE THE DRAWING.WPB
 AMEND. TO FBC SEC. 107.2.1.
 45) SHTS. P803 & P804 - HOSE BIBBS SHALL BE SEPARATELY
 VALVED PER FBC-PLUMBING SEC.606.2 (2).
 46) SHT. P803 - SHOW THE 1/2 INCH DHR LINE BY STORAGE
 ROOM EQ1.11 ON THE WATER RISER.
 47) SHT. P804 - IDENTIFY THE WASHING MACHINE IN THE
 STAFF LAUNDRY ON THE WATER RISER.(EQUIPMENT ROOM EQ
 1.2).
 48) THE PLUMBING SHEETS SHOW SERVICE SINKS ON LEVELS 2,
 3 & 4 BUT THEY ARE NOT SHOWN ON THE ARCHITECTURAL
 PLANS. CLARIFY.
 49) SHTS. P803 & P804 - DOWNFEED RISERS SHALL BE
 EQUIPPED WITH FULLL OPEN SHUTOFF VALVES PER
 FBC-PLUMBING SEC.606.1 (5).
 50) SHT. P803 - IDENTIFY THE WASHING MACHINE IN THE
 GUEST LAUNDRY ON THE WATER RISER.
 51) SHUTOFF VALVES ARE REQUIRED AT THE BASE OF RISERS 3
 INCH DHW & 4 INCH DCW
 52) THE FLOOR DRAIN IN THE ELEVATOR SHAFT SHALL BE
 INDIRECTLY CONNETED TO THE PLUMBING SYSTEM PER
 FBC-PLUMBING SEC. 3301.6.
 53) INDICATE ON THE PLAN IF THE ELEVATOR IS HYDRAULIC
 OR TRACTION TYPE. IF HYYDRAULIC, THE INSTALLATION OF
 THE FLOOR DRAIN IN THE PIT SHALL OMPLY WITH
 FBC-PLUMBING SEC.1003.4.
 54) SUBMIT A DETAIL OF THE GREASE INTERCEPTOR. THE
 GREASE INTERCEPTOR SHALL COMPLY WITH THE FL. ADMIN.CODE
 RULE 64E-6 AND THE CITY OF WEST PALM BEACH STANDARD
 DETAIL GS-7. CONTACT THE CITY'S ENGINEERING DEPT. AT
 561-494-1040 FOR FURTHER INFORMATION ON TANDARDD
 DRAWING GC-7.
 55) SWAY BRACING SHALL BE PROVIDED AT CHANGES IN
 DIRECTION GREATER THAN 45 DEGREES FOR DRAINAGE PIPE
 SIZES 4 INCHES AND LARGER PER FBC-PLUMBING SEC.308.6.
 SUBMIT DETAIL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW