| 2020-10-30 07:55:50 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20090848 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC EC |
| | C403.2.1; FBC M 312.1 |
| | |
| | 2) SHEET A031 INDICATES A 2-HOUR RATED WALL FOR THE |
| | STORAGE AREA WHERE AHU-1 IS LOCATED (M201). IT APPEARS |
| | THAT THE AREA ABOVE THE CEILING IS BEING USED AS A |
| | RETURN AIR PLENUM. PLEASE SHOW THE RETURN AIR PATH BACK |
| | TO AHU-1 IN THIS AREA. FBC M 601.6 |
| | |
| | 3) SHEET M201: PLEASE SHOW THE PROTECTION OF THE DRYER |
| | DUCT PENETRATION IN THE RATED WALL AT THE GUEST |
| | LAUNDRY. FBC M 504.2 |
| | |
| | 4) GUEST ROOM BATH EXHAUST FANS: |
| | .RATES ARE PER ROOM UNLESS OTHERWISE INDICATED. THE |
| | HIGHER RATE SHALL BE PROVIDED WHERE THE EXHAUST SYSTEM |
| | IS DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER RATE |
| | SHALL BE PERMITTED ONLY WHERE THE EXHAUST SYSTEM IS |
| | DESIGNED TO OPERATE CONTINUOUSLY WHILE OCCUPIED. FBC M |
| | TABLE 403.3.1.1 NOTE F |
| | |
| | 5) PLEASE SHOW THE PENETRATION PROTECTION AT THE |
| | PENETRATION OF THE RATED WALL AT DUCT FOR THE EXHAUST |
| | FAN IN THE CHUTE ROOM ON FLOORS 2, 3 AND 4. FBC M 607.5 |
| | |
| | 6) SHEET A440: PANTRY EQUIPMENT LEGEND, NOTE 10 IS AN |
| | OVEN. PLEASE PROVIDE SPECIFICATIONS FOR THIS OVEN AND |
| | EXPLAIN HOW IT WOULD MEET FBC M 507.1 |
| | |
| | 7) SHEET A440: PANTRY EQUIPMENT LEGEND, NOTE 3 IS A |
| | DISHWASHER. PLEASE PROVIDE SPECIFICATIONS FOR THIS |
| | DISHWASHER AND EXPLAIN HOW IT WOULD MEET FBC M 507.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |