Plan Review Notes
Plan Review Notes For Permit 20090848
Permit Number 20090848
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-10-26 13:01:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP001 - THERE ARE INCORRECT FIRE CODE
 REFERENCES UNDER SECTION 1. CODES AND STANDARDS
  
 THE FIRE SPRINKLER INSTALLATION SHALL COMPLY WITH THE
 CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE ,
 6TH ED., 2015 NFPA 1 & 101
  
 NFPA 13, 24 & 72 2013 EDITIONS
  
 PLEASE REVIEW AND CORRECT ALL FP SHEETS
  
  
  
 2) SHEET FP001 - ALL FIRE SPRINKLER FIRE WORK SHALL BE
 INSTALLED PER NFPA 13 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
 2A) SHEET FP002 - THERE IS NO INDICATION OF FIRE
 SPRINKLER PROTECTION UNDER THE PORTE COCHERE.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET FP001 - THERE IS AN INDICATION OF UNDERGROUNG
 FIRE LINE WORK. ALL UNDERGROUND FIRE LAINE WORK,
 INCLUDING THE FIRE LINE TAP, DDCV AND FDC SHALL BE
 INSTALLED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
  
 4) THERE DOES NOT APPEAR TO BE STANDPIPES INSTALLED IN
 EACH STAIRWELLS. STANDPIPES ARE REQUIRED UNDER THE
 FLORIDA BUILDING CODE AND INSTALLED PER NFPA 14.
  
  
 PLEASE PROVIDE AND CORRECT.
  
  
  
 5) SHEET #121 - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT. ALL FIRE ALARM WORK SHALL BE
 INSTALLED PER NFPA 72 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
  
 6) SHEET A031 - UNDER SECTION CHAPTER 9 - FIRE
 PROTECTION SYSTEMS, THERE IS AN INDICATION OF A
 COMMERCIAL HOOD AND DUCT SYSTEM AND TYPE I HOOD, ANY
 REQUIRED HOOD SYSTEM SHALL BE INSTALLED PER NFPA 96
 UNDER SEPARATE PERMITS, 1 FOR THE HOOD AND 1 FOR THE
 SUPPRESSION, AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT.
  
  
  
 7) FP SHEETS - THERE DOES NOT APPEAR TO BE FIRE
 SPRINKLERS WITHIN THE LAUNDRY CHUTE.
  
 PER NFPA 82
  
 6.2.6 AUTOMATIC SPRINKLERS.
 6.2.6.1 GRAVITY CHUTE.
 6.2.6.1.1 GRAVITY CHUTES SHALL BE PROTECTED INTERNALLY
 BY AUTOMATIC
 SPRINKLERS UNLESS THE CHUTE IS IN ACCORDANCE WITH
 6.2.2.5
 OR 6.2.2.6.
 6.2.6.1.2 A SPRINKLER SHALL BE INSTALLED AT OR ABOVE
 THE TOP
 CHUTE INTAKE OF THE CHUTE.
 6.2.6.1.3 AUTOMATIC SPRINKLERS INSTALLED IN GRAVITY
 CHUTE INTAKES
 SHALL BE RECESSED OUT OF THE CHUTE AREA THROUGH WHICH
 THE MATERIAL TRAVELS.
 6.2.6.1.4 A SPRINKLER SHALL BE INSTALLED WITHIN THE
 CHUTE AT
 ALTERNATE FLOOR LEVELS IN CHUTES CONNECTING MORE THAN
 TWO STORIES,
 WITH A MANDATORY SPRINKLER LOCATED AT THE LOWEST
 SERVICE
 LEVEL.
 6.2.6.1.5 SPRINKLER SYSTEM INSTALLATION SHALL COMPLY
 WITH
 NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  