| 2020-10-26 13:01:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP001 - THERE ARE INCORRECT FIRE CODE |
| | REFERENCES UNDER SECTION 1. CODES AND STANDARDS |
| | |
| | THE FIRE SPRINKLER INSTALLATION SHALL COMPLY WITH THE |
| | CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE , |
| | 6TH ED., 2015 NFPA 1 & 101 |
| | |
| | NFPA 13, 24 & 72 2013 EDITIONS |
| | |
| | PLEASE REVIEW AND CORRECT ALL FP SHEETS |
| | |
| | |
| | |
| | 2) SHEET FP001 - ALL FIRE SPRINKLER FIRE WORK SHALL BE |
| | INSTALLED PER NFPA 13 UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. |
| | |
| | |
| | 2A) SHEET FP002 - THERE IS NO INDICATION OF FIRE |
| | SPRINKLER PROTECTION UNDER THE PORTE COCHERE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET FP001 - THERE IS AN INDICATION OF UNDERGROUNG |
| | FIRE LINE WORK. ALL UNDERGROUND FIRE LAINE WORK, |
| | INCLUDING THE FIRE LINE TAP, DDCV AND FDC SHALL BE |
| | INSTALLED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. |
| | |
| | |
| | |
| | 4) THERE DOES NOT APPEAR TO BE STANDPIPES INSTALLED IN |
| | EACH STAIRWELLS. STANDPIPES ARE REQUIRED UNDER THE |
| | FLORIDA BUILDING CODE AND INSTALLED PER NFPA 14. |
| | |
| | |
| | PLEASE PROVIDE AND CORRECT. |
| | |
| | |
| | |
| | 5) SHEET #121 - THERE ARE INDICATIONS OF FIRE ALARM |
| | DEVICES/EQUIPMENT. ALL FIRE ALARM WORK SHALL BE |
| | INSTALLED PER NFPA 72 UNDER SEPARATE PERMIT AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. |
| | |
| | |
| | |
| | 6) SHEET A031 - UNDER SECTION CHAPTER 9 - FIRE |
| | PROTECTION SYSTEMS, THERE IS AN INDICATION OF A |
| | COMMERCIAL HOOD AND DUCT SYSTEM AND TYPE I HOOD, ANY |
| | REQUIRED HOOD SYSTEM SHALL BE INSTALLED PER NFPA 96 |
| | UNDER SEPARATE PERMITS, 1 FOR THE HOOD AND 1 FOR THE |
| | SUPPRESSION, AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWEDGEMENT. |
| | |
| | |
| | |
| | 7) FP SHEETS - THERE DOES NOT APPEAR TO BE FIRE |
| | SPRINKLERS WITHIN THE LAUNDRY CHUTE. |
| | |
| | PER NFPA 82 |
| | |
| | 6.2.6 AUTOMATIC SPRINKLERS. |
| | 6.2.6.1 GRAVITY CHUTE. |
| | 6.2.6.1.1 GRAVITY CHUTES SHALL BE PROTECTED INTERNALLY |
| | BY AUTOMATIC |
| | SPRINKLERS UNLESS THE CHUTE IS IN ACCORDANCE WITH |
| | 6.2.2.5 |
| | OR 6.2.2.6. |
| | 6.2.6.1.2 A SPRINKLER SHALL BE INSTALLED AT OR ABOVE |
| | THE TOP |
| | CHUTE INTAKE OF THE CHUTE. |
| | 6.2.6.1.3 AUTOMATIC SPRINKLERS INSTALLED IN GRAVITY |
| | CHUTE INTAKES |
| | SHALL BE RECESSED OUT OF THE CHUTE AREA THROUGH WHICH |
| | THE MATERIAL TRAVELS. |
| | 6.2.6.1.4 A SPRINKLER SHALL BE INSTALLED WITHIN THE |
| | CHUTE AT |
| | ALTERNATE FLOOR LEVELS IN CHUTES CONNECTING MORE THAN |
| | TWO STORIES, |
| | WITH A MANDATORY SPRINKLER LOCATED AT THE LOWEST |
| | SERVICE |
| | LEVEL. |
| | 6.2.6.1.5 SPRINKLER SYSTEM INSTALLATION SHALL COMPLY |
| | WITH |
| | NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER |
| | SYSTEMS. |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |