2020-11-02 07:22:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 E-301
  
 1) GFCI RECEPTACLES HAVE DESIGNATIONS OF B, C, C, D,
 AND E WHAT DO THEY STAND FOR?
  
 E-302
  
 1) QQ SUITE, QQ ACCESSIBLE, QQ ACCESSIBLE 2-BAY HAVE NO
 USB OUTLETS NOT A CODE REQUIREMENT JUST AN OBSERVATION.
  
 E-401
  
 1) 3000A MAIN NEEDS TO COMPLY WTH 240.87, PLEASE
 INDICATE HOW THIS WILL BE DONE.
  
 2) FAULT CURRENT RATING OF THE SERVICE AND PANELS NEEDS
 TO BE CALCULATED 110.9, 110,10 AND LABELS APPLIED PER
 110.24
  
 4) PANEL EM HAS THE FIRE PUMP AND ELEVATORS INSTALLED
 IN IT, HOW DOES THIS MEET THE REQUIREMENTS OF 695.4(B),
 AND 695.4 (B)(3)(A) & (B)
  
 NOTE
  
 THE FOLLOWING SYSTEMS REQUIRE SEPARATE PERMITS
 LIGHTNING PROTECTION, BDA, FIRE ALARM, SITE LIGHTING,
 GENERATOR AND ANY LOW VOLTAGE SYSTEMS.