| Plan Review Notes For Permit 20090848 |
| Permit Number |
20090848 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-02 07:22:31 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | E-301 | | | | | | 1) GFCI RECEPTACLES HAVE DESIGNATIONS OF B, C, C, D, | | | AND E WHAT DO THEY STAND FOR? | | | | | | E-302 | | | | | | 1) QQ SUITE, QQ ACCESSIBLE, QQ ACCESSIBLE 2-BAY HAVE NO | | | USB OUTLETS NOT A CODE REQUIREMENT JUST AN OBSERVATION. | | | | | | E-401 | | | | | | 1) 3000A MAIN NEEDS TO COMPLY WTH 240.87, PLEASE | | | INDICATE HOW THIS WILL BE DONE. | | | | | | 2) FAULT CURRENT RATING OF THE SERVICE AND PANELS NEEDS | | | TO BE CALCULATED 110.9, 110,10 AND LABELS APPLIED PER | | | 110.24 | | | | | | 4) PANEL EM HAS THE FIRE PUMP AND ELEVATORS INSTALLED | | | IN IT, HOW DOES THIS MEET THE REQUIREMENTS OF 695.4(B), | | | AND 695.4 (B)(3)(A) & (B) | | | | | | NOTE | | | | | | THE FOLLOWING SYSTEMS REQUIRE SEPARATE PERMITS | | | LIGHTNING PROTECTION, BDA, FIRE ALARM, SITE LIGHTING, | | | GENERATOR AND ANY LOW VOLTAGE SYSTEMS. |
|