| Date |
Text |
| 2020-10-01 08:52:45 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20090847 |
| | 10/1/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WERE NOT |
| | ADDRESSED. PLEASE COMPLY WITH THE COMMENTS AND SUBMIT A |
| | NARRATIVE RESPONSE WITH THE CORRECTED PLANS AS |
| | PREVIOUSLY REQUESTED. IF YOU WOULD LIKE TO DISCUSS THE |
| | COMMENTS PLEASE CONTACT ME AT YOUR EARLIEST |
| | CONVENIENCE- SEE CONTACT INFO BELOW. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 240 30TH ST. |
| | SHOW GAS PERMIT #04090117 ISSUED ON 11/15/04 FOR GAS |
| | LINE INSTALLATION TO A NEW WATER HEATER AT 165,000 |
| | BTUH, AND A NEW RANGE AT 72,000 BTUH. PLEASE REVISE THE |
| | GAS RISER TO SHOW A COMPLETE PIPING SYSTEM THAT |
| | INCLUDES THE NEW APPLIANCES AND THE EXISTING- SECTIONS |
| | G2412.3 & G2412.4 FBC RES. PLEASE NOTE I COULD NOT FIND |
| | A PERMIT OR ANY INFORMATION ABOUT THE POOL HEATER WHICH |
| | IS SHOWN AS EXISTING ON YOUR RISER DRAWING. ANY |
| | APPLIANCE CONNECTED TO THE SYSTEM THAT WAS NOT |
| | PREVIOUSLY PERMITTED SHALL BE REVIEWED AS A NEW |
| | INSTALLATION. PLEASE SHOW THE BTUH LOAD OF THE POOL |
| | HEATER ALONG WITH THE OTHER NEW AND EXISTING |
| | APPLIANCES. |
| | |
| | A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| | OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. |
| | |
| | B) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN |
| | AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM- |
| | SECTIONS G2413.4.1 AND G2413.4.2 FBC RES. PLEASE NOTE |
| | THAT THE RECORD DRAWING SHOWS THE TOTAL DEVELOPED |
| | LENGTH TO BE 78 FT. |
| | |
| | D) PLEASE INDICATE THE SIZING METHOD USED PER SECTIONS |
| | G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH LENGTH. |
| | INDICATE THE TABLES USED TO SIZE THE PIPING- SEE TABLES |
| | G2413.4(1)- G2413.4(8). |
| | |
| | E) SHOW THE DELIVERY PRESSURE AT THE EXISTING METER- |
| | G2413.1. |
| | |
| | F) SHOW THE LOCATIONS OF SHUT OFF VALVES AND PIPE |
| | UNIONS- SECTIONS G2420.5 & G2422.1.4. |
| | |
| | G) SHOW THE LOCATIONS OF NEW AND EXISTING REGULATORS. |
| | INDICATE THE MAKES AND MODELS OF THE REGULATORS AND |
| | THEIR INLET AND OUTLET PRESSURES- SECTION G2421.1 & |
| | 2421.2. SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING |
| | THE SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, SPRING DATA, AND ORIFICE SIZE. PLEASE NOTE |
| | THE SPECS MAY BE DEFERRED AND ONSITE FOR INSPECTION- |
| | SECTION- 107.2.1 & 107.3.4.1 FBC RES. |
| | |
| | H) SHOW THE LOCATIONS OF DRIP LEGS- SECTION G2419.2. |
| | |
| | I) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL NEW |
| | APPLIANCES- SECTIONS G2404.3 AND G2431.1. PLEASE MARKUP |
| | THE SPECS TO SHOW THE LISTING OF THE APPLIANCE, BTUH |
| | LOAD, AND INPUT PRESSURE RATING. PLEASE NOTE THAT THE |
| | REQUESTED PRODUCT SPECS MAY BE DEFERRED AND ONSITE FOR |
| | INSPECTION- SECTION 107.1 & 107.3.4.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |