| 2020-10-05 09:37:38 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090828 |
| | 9/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISED GAS RISER: |
| | |
| | A) PROVIDE THE PIPE SIZING TABLE FOR THE 1 IN. PE |
| | PIPING. IF YOU ARE USING THE LOW PRESSURE TABLES IN THE |
| | FBC FG, BOTH LOW PRESSURE TABLES- 402.4(20) OR |
| | 402.4(21) INDICATE THE 1.25, 1, AND ? IN. PE PIPES ARE |
| | UNDERSIZED. |
| | |
| | B) TABLE 402.4(4) FOR THE GALVANIZED PIPE HAS A HIGH |
| | PRESSURE DROP OF 6.0 IN. W.C. WHICH IS A HIGH DROP FOR |
| | A RESIDENTIAL SYSTEM WHICH TYPICALLY HAS APPLIANCES |
| | WITH LOW PRESSURE INPUTS AROUND 5- 7 IN.W.C. PLEASE |
| | REFER TO SECTION 402.5 FBC FG, OR SECTION G2413.5 FBC |
| | RES. FUEL GAS. |
| | |
| | C) IT APPEARS THE ADDITIONAL LOAD OF THE GENERATOR MAY |
| | REQUIRE EITHER THE PE EXISTING PIPES TO BE INCREASED IN |
| | SIZE, OR THE METER MAY REQUIRE AN UPGRADE TO A 2 PSI |
| | SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |