| 2021-02-11 12:18:44 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20090819 |
| | 2/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | 2ND REVIEW COMMENTS BASED ON NEW ARCHITECTURAL AND |
| | PLUMBING PLANS. |
| | |
| | 1) PLUMBING PLAN: PROVIDE SANITARY DRAINAGE AND VENT |
| | ISOMETRIC DRAWINGS FOR THE NEW AND REMODELED BATHROOMS, |
| | BAR, KITCHEN AND LAUNDRY ROOMS- SECTION 107.3.5.3 WPB. |
| | |
| | 2) P PLAN: PROVIDE A CLEANOUT AT THE JUNCTION OF BATH |
| | #5 DRAIN AND THE SEWER LINE- SECTION P3005.2.3 FBC RES. |
| | |
| | 3) P PLAN: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| | WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | SECTION G2448.1 FBC RES. |
| | |
| | 4) THE PLUMBING CONTRACTOR OF RECORD WHO PREPARED THE |
| | PLUMBING DRAWING SHALL SUBMIT A PLUMBING SUB-PERMIT |
| | APPLICATION- SECTION 105.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |