| 2021-02-11 12:48:22 | 1ST REVIEW FBC-2017 RES. FUEL GAS. |
| | PERMIT- 20090819 |
| | 2/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P PLAN: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| | WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | SECTION G2448.1 FBC RES. PLEASE NOTE COMPLETE |
| | SPECIFICATIONS AND INSTALLATION MANUAL SHALL BE ONSITE |
| | AT TIME OF INSPECTION, AND THAT AN ADDITIONAL PRESSURE |
| | REGULATOR MAY BE REQUIRED AT THE WATER HEATER BASED ON |
| | MANUFACTURER'S INPUT PRESSURE SPECIFICATION. |
| | |
| | 2) P PLAN: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | NEW RANGE SHOWING BTUH LOAD AND INPUT PRESSURE- SECTION |
| | G2447.1 FBC RES. PLACE A NOTE ON THE PLAN TO INDICATE |
| | ACCESS SHALL BE PROVIDED TO THE APPLIANCE SHUTOFF |
| | VALVE- G2450.5.1 FBC RES. |
| | |
| | 3) THE GAS CONTRACTOR OF RECORD WHO PREPARED THE GAS |
| | RISER DRAWING SHALL SUBMIT A GAS SUB-PERMIT |
| | APPLICATION- SECTION 105.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |