Plan Review Notes
Plan Review Notes For Permit 20090816
Permit Number 20090816
Review Stop P
Sequence Number 2
Notes
Date Text
2020-10-01 12:48:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090816 6501 N JOG RD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PER WPB FBC 107.1, THE DESIGN PROFESSIONAL SHALL
 PROVIDE HIS OR HER OFFICIAL SEAL/DIGITAL SIGNATURE TO
 THE PLANS AS REQUIRED BY FLORIDA STATUTES.
  
 2.A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3.ON YOUR COVER SHEET UNDER THE DRAWING INDEX IT HAS A
 SHEET THAT IS MISSING FOR EXAMPLE SHEET G002, G-003,
 C001, C002, C003, AND C004, PLEASE SUBMIT MISSING PAGES
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4.THIS APPEARS TO BE REPLACEMENT OF EXISTING PIPING AND
 WELLHEAD WITH NEW. IS THE WELLHEAD (REFERENCE
 C-CONCRETE REPAIR, PLAN SHEET C-004) NEW OR EXISTING?
 PER WPB FBC 107.2.1, CLARIFY.
  
 5.REGARDING P-ABOVEGROUND PLUMBING (PLAN SHEET C-005;
 PERMIT APPLICATION IS FOR NEW WELL HEAD AND ABOVEGROUND
 PIPING, BUT PLAN PROVIDES DETAILS FOR EXCAVATION AND
 DISCHARGE TO MANHOLE. CLEARLY INDICATE ON THE PLAN THE
 FULL SCOPE OF THE NEW PIPING AND PROVIDE POINT(S) OF
 CONNECTION TO EXISTING.
  
 6.PER WPB FBC 107.2.1, PROVIDE SITE PLAN SHOWING
 LOCATION OF WELLHEAD, EXISTING DISCHARGE MANHOLE AND
 ROUTING OF DISCHARGE PIPING FROM WELLHEAD TO MANHOLE.
 SHOW POINT(S) OF CONNECTION FOR NEW TO ANY E
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  