| 2020-09-29 17:06:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20090811 1117 N OLIVE AVE # 101 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER FBC 1210.2.2, WALLS AND PARTITIONS WITHIN 2 FEET |
| | (610 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS |
| | SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A |
| | HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND |
| | EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN |
| | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY |
| | AFFECTED BY MOISTURE. PAINTED WALLS DO NOT COMPLY. |
| | REVISE THE ROOM FINISH SCHEDULE ON PLAN SHEET A-3 TO |
| | COMPLY. |
| | |
| | 2.PROVIDE CLEAR FLOOR SPACE FOR BREAKROOM SINK. IF |
| | PARALLEL APPROACH, SINK SHALL BE CENTERED ON THE SPACE. |
| | IF FORWARD APPROACH, CABINET AND SINK SHALL BE |
| | CONSTRUCTED TO COMPLY WITH FBC ACC 306 FOR KNEE AND TOE |
| | CLEARANCE AND SHALL ACCOMMODATE THE FULL WIDTH OF THE |
| | REQUIRED 30 X 48 CLEAR FLOOR SPACE. |
| | |
| | 3.PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT LEAST |
| | 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| | PROVIDE MINIMUM OF ONE ACCESSIBLE EXAM ROOM SINK AND |
| | PROVIDE CLEAR FLOOR SPACE FOR ACCESSIBLE SINK. |
| | |
| | 4.PER WPB FBC 107.2.1, AS A DRINKING FOUNTAIN IS NOT |
| | REQUIRED BASED ON OCCUPANT LOAD AND NOT BEING PROVIDED, |
| | DELETE REFERENCES TO SAME ON PLAN SHEET A-3. |
| | |
| | 5.PER WPB FBC 107.2.1, CLARIFY THE WATER CLOSET SHALL |
| | BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND |
| | TO ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL |
| | BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE |
| | WALL OR PARTITION PER FBC ACC 604.2 |
| | |
| | 6.PER WPB FBC 107.2.1, CLARIFY TOILET PAPER DISPENSERS |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE |
| | LOCATED BEHIND GRAB BARS PER FBC ACC 604.8. |
| | |
| | 7.PLEASE NOTE THAT THE IN-LINE VALVE FOR THE HOT WATER |
| | RESTROOM WHEN IN THE OFF POSITION EFFECTIVELY KILLS THE |
| | HOT WATER RECIRCULATION. PROVIDE DEDICATED VALVED HOT |
| | WATER DROP TO LAVATORY FROM RECIRCULATED LINE TO COMPLY |
| | WITH FBC PL 606.1. |
| | |
| | 8.RE: WATER HEATER DETAIL |
| | A.PER FBC PL 607.3, WHERE A STORAGE WATER HEATER IS |
| | SUPPLIED WITH COLD WATER THAT PASSES THROUGH A CHECK |
| | VALVE, PRESSURE REDUCING VALVE OR BACKFLOW PREVENTER, A |
| | THERMAL EXPANSION CONTROL DEVICE SHALL BE CONNECTED TO |
| | THE WATER HEATER COLD WATER SUPPLY PIPE AT A POINT THAT |
| | IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING |
| | VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION |
| | CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH |
| | THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM |
| | SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8. |
| | B.PER FBC PL 504.6, PROVIDE AN AIR GAP FOR THE T & P |
| | RELIEF DISCHARGE TO THE PAN. |
| | C.PER FBC PL 504.2, BOTTOM FED WATER HEATERS AND BOTTOM |
| | FED TANKS CONNECTED TO WATER HEATERS SHALL HAVE A |
| | VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF VALVE |
| | SHALL COMPLY WITH ANSI Z21.22. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS OR DIGITALLY SIGNED AND SEALED |
| | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |