| 2020-09-23 16:38:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | DOES NOT LOOK LIKE MINOR CHANGES!!!! |
| | |
| | 1) OUTLET SPACING ON KITCHEN, PANTRY, AND LAUNDRY ROOM |
| | COUNTER SPACES. |
| | |
| | E3901.4 COUNTERTOP RECEPTACLES. |
| | IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| | SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| | COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTIONS E3901.4.1 THROUGH E3901.4.5 |
| | |
| | 2) SMOKE/CO ALARMS MISSING FROM GUEST ROOM, AND BED |
| | ROOMS R314, R315 FBC RESIDENTIAL |
| | |
| | 3) NEED RISER DIAGRAM AND LOAD CALCULATION 215.5 |
| | |
| | 4) DECKS AND BALCONIES NEED OUTLETS. 210.53 |
| | |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM |
| | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] |