| 2020-10-05 13:23:26 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090781 |
| | 9/24/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE APPROVED GENERATOR PERMIT AND PLANS UNDER |
| | PERMIT- 20080051 WAS FOR A 27 KW GENERATOR. PLEASE |
| | CORRECT THE RISER TO SHOW THE CORRECT 359,000 BTUH LOAD |
| | AS INDICATED IN THE GENERATOR SPECS SUBMITTED WITH THE |
| | PERMIT. |
| | |
| | 2) THE GENERATOR SPECS SHOW A NATURAL GAS INPUT |
| | PRESSURE OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING |
| | SHOWS A REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE |
| | TO THE GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE |
| | AND MODEL OF THE SELECTED REGULATOR ON THE RISER. |
| | SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING |
| | THE MODEL, INLET AND OUTLET PRESSURES, SPRING |
| | SELECTION, AND ORIFICE SIZE- SECTION G2421.1 & G2421.2. |
| | SHOW THE REQUIRED PIPE UNIONS AT THE REGULATOR. |
| | |
| | 3) THERE IS A 0 VALUE FOR THE PROPOSED GAS PIPING |
| | INSTALLATION. PLEASE SUBMIT A COPY OF A SIGNED CONTRACT |
| | AND/OR COPIES OF INVOICES AND ESTIMATES SHOWING THE |
| | TOTAL COST OF THE INSTALLATION INCLUDING VALUE OF |
| | LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN FEES, |
| | AND OVERHEAD AND PROFIT- SECTION 109.3 WPB. IF THE COST |
| | OF THE GAS INSTALLATION WAS INCLUDED IN THE GENERATOR |
| | PERMIT, PLEASE PROVIDE COPIES OF THE PRIMARY AND |
| | SUB-CONTRACTS TO VERIFY. |
| | |
| | 4) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT) |
| | SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM |
| | COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF |
| | 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND |
| | DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |