| Date |
Text |
| 2020-09-24 11:14:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090781 |
| | 9/24/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC DRAWING: |
| | |
| | A) SHOW THE LENGTH, THE TYPE, AND SIZE OF PIPING FROM |
| | THE METER TO THE 1-1/2" TEE, FROM THE 1-1/2" TEE TO THE |
| | 1-1/4" TEE, AND FROM THE 1-1/4" TEE TO THE PIPE |
| | ENTRANCE INTO THE BUILDING. PLEASE CLARIFY IF THE |
| | 1-1/4" TEE IS A REDUCER FITTING AND NOT A TEE BECAUSE A |
| | SECOND BRANCH LINE IS NOT SHOWN ON THE RISER- SECTIONS |
| | G2413.4.1 FBC RES. |
| | B) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS |
| | FOR THE INTERIOR APPLIANCES AND THE POOL HEATER- |
| | SECTION G2421.1 & G2421.2 FBC RES. |
| | C) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. THE |
| | UPDATED SPECS FOR THE GENERAC 22KW MODEL INDICATE A |
| | FULL LOAD OF 306,000 BTUH FOR NATURAL GAS. PLEASE |
| | CORRECT THE LOAD SHOWN ON THE RISER. |
| | D) THE GENERAC SPECS SHOW A NATURAL GAS INPUT PRESSURE |
| | OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING SHOWS A |
| | REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE TO THE |
| | GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE AND |
| | MODEL OF THE SELECTED REGULATOR ON THE RISER. SUBMIT |
| | MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING THE |
| | MODEL, INLET AND OUTLET PRESSURES, SPRING SELECTION, |
| | AND ORIFICE SIZE- SECTION G2421.1 & G2421.2. SHOW THE |
| | REQUIRED PIPE UNIONS AT THE REGULATOR. |
| | E) INDICATE HOW THE PE PIPING RISER WILL MAKE |
| | CONNECTION TO THE EXISTING PIPING AT THE BBQ- SECTIONS |
| | G2415.17.1 & G2415.17.2. PLEASE NOTE THAT SPECS FOR |
| | ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS SHALL |
| | BE LISTED AND LABELED. |
| | F) INDICATE A DRIP LEG WILL BE INSTALLED AND HOW THE |
| | LOCATION- SECTION G2419.2 FBC RES. |
| | G) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| | CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| | STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| | G2415.1. |
| | |
| | 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT) |
| | SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM |
| | COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF |
| | 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND |
| | DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |