| 2020-09-29 10:27:53 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE VALUE OF $4875.00 IS LOW FOR THE SCOPE OF WORK |
| | TO RELACE 12 WINDOWS AND 2 DOORS WITH IMPACT RATED. |
| | SUBMIT A COPY OF THE SIGNED CONTRACT TO VERIFY. FBC |
| | 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) CIRCLE OR HI-LIGHT THE APPROPRIATE ITEMS, SUCH AS |
| | SIZE, GLASS TYPE, DESIGN PRESSURE, THAT APPLY TO THE |
| | PROJECT ON THE PRODUCT APPROVAL. FBC 107.2 |
| | |
| | 3) THE PRODUCT APPROVAL COVERSHEETS FOR THE SINGLE HUNG |
| | (FL22250-R2) AND HORIZONTAL ROLLING (FL21557-R2) |
| | WINDOWS ARE MISSING THE PAGES THAT LIST THE DRAWING |
| | NUMBERS. FAC RULE 61G20 |
| | |
| | 4) THE ENTIRE COVERSHEETS WITH THE FL NUMBERS AND |
| | DRAWING NUMBERS ARE MISSING FOR THE FIXED WINDOW AND |
| | THE SLIDING GLASS DOOR. FAC RULE 61G20 |
| | |
| | |