| 2020-10-24 10:22:45 | PLAN REVIEW GENERATOR / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RE: GENERATOR PAD AND DESIGN WIND LOADS |
| | |
| | 1) PROVIDE GENERATOR PAD WITH STRUCTURAL DETAILS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY THE |
| | DESIGNER. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |
| | 3) PROVIDE WIND DESIGN PRESSURE REQUIREMENTS. |
| | |
| | NOTE: ASSUMED DESIGN CRITERIA FOR THIS SITE: VULT OF |
| | 170MPH, (FIGURE R301.2(4) ) VASD OF 132MPH (TABLE |
| | R301.2.1.3) RISK CATEGORY I AND EXPOSURE CATEGORY C. |
| | |
| | 4) PROVIDE WIND DESIGN PRESSURES FOR GENERATOR. |
| | EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE DESIGNED |
| | PER FBC RES CHPT 3 SECTION R301 OR ASCE 7 |
| | |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | 5) LOCATION OF GENERATOR ON SURVEY STATES IT SHALL BE |
| | LOCATED 5 FEET FROM WINDOWS/DOORS/VENTS. GENERATOR |
| | SHALL BE LOCATED AT LEAST 10 FEET FROM BUILDING |
| | OPENINGS. |
| | R303.5.1 INTAKE OPENINGS. |
| | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM |
| | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, |
| | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS |
| | AND LOADING DOCKS. |
| | |
| | |
| | |
| | |
| | |