| Date |
Text |
| 2020-11-17 07:50:41 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20090720 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ONCE THE M-1 SHEETS THAT IS PERTANENT TO THIS |
| | SPECIFIC PROJECT I CAN COMPLETE THE REVIEW. THERE ARE 2 |
| | DIFFERENT M-1 SHEETS. THE ONE IS FROM PREMIER |
| | CONSULTING ENGINEERS. IT APPEARS TO MATCH THE A SHEETS |
| | AS IT HAS 2 AHU?S AND 2 CONDENSERS. THE OTHER IS FROM |
| | KAREN OLIVER. IT IS NOT CONSISTENT WITH THE A SHEETS AS |
| | IT SHOWS 1 AHU ON THE SECOND STORY THAT ALSO SUPPLIES |
| | AIR TO THE GROUND FLOOR. PLEASE REMOVE FROM THE |
| | SUBMITTED SHEETS THE M-1 SHEET THAT DOES NOT APPLY TO |
| | THIS PROJECT. FBC 107.2.1 |
| | |
| | 2) PLEASE PROVIDE THE REFERENCED HOOD RANGE CUT SHEET |
| | SPECIFICATIONS, I DO NOT SEE THE DOCUMENT IN THIS |
| | SUBMITTAL. FBC 107.2.1 |
| | |
| | 3) THE PREMIER CONSULTING M-1 SHEET INDICATES THAT THE |
| | 2 ACCU?S ARE 1.5 TONS. THE EQUIPMENT SIZING |
| | CALCULATIONS REQUIRES 3.34 TONS. PLEASE BE CONSISTENT. |
| | FBC RES M1401.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |